| 2022-02-09 13:08:15 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21110232 |
| | 2/9/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| | CAPS FOR FURTHER CLARIFICATION. |
| | |
| | 1) FAILED. G110: THE PLAN APPEARS TO SHOW THE OCCUPANT |
| | LOAD OF THE STORY HAS INCREASED OVER 20%. REFER TO SEC. |
| | 810.1 FBC EX AND PROVIDE PLUMBING FIXTURE CALCULATIONS |
| | IN COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A |
| | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED |
| | NUMBER OF PLUMBING FIXTURES. PLEASE NOTE THAT DRINKING |
| | FOUNTAINS AND SERVICE SINKS ARE REQUIRED FOR B |
| | OCCUPANCIES. THE CALCULATIONS AND PLANS ARE NOT IN |
| | COMPLIANCE WITH TABLE 403.1 FBC WHICH REQUIRES A |
| | MINIMUM OF 3 MALE WATER CLOSETS AND 2 MALE LAVATORIES. |
| | PLEASE NOTE SEPARATE FACILITIES ARE REQUIRED FOR MALE |
| | AND FEMALE USE- SEC. 403.2 |
| | |
| | 6) FAILED. P-200: PLEASE SHOW THE LOCATIONS OF THE |
| | REQUIRED CHECK VALVES AND FULL OPEN VALVES ON THE PUMP |
| | DISCHARGE PIPES AND SHOW HOW ACCESS TO THE VALVES WILL |
| | BE PROVIDED- SEC. 712.2 FBC P. THE CORRECTED SHEET |
| | P-200 WAS NOT RESUBMITTED FOR REVIEW. |
| | |
| | NEW COMMENT. |
| | |
| | 1) SHEET P-201: HOT WATER AT A MINIMUM TEMPERATURE OF |
| | 110 DEGREES REQUIRED F AT THE NEW SINKS PER SECS. 202 & |
| | 607.1 FBC P. PLACE A NOTE ON THE WATER HEATER EQUIPMENT |
| | SCHEDULE OR SUBMIT SPECS TO VERIFY THE EEMAX WATER |
| | HEATERS DO NOT HAVE INTEGRAL DEVICES THAT WILL LIMIT |
| | THE WATER TEMPERATURE TO LESS THAN 110 DEGREES F. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |