| 2022-01-05 16:24:45 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21110232 |
| | 1/5/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) G110: THE PLAN APPEARS TO SHOW THE OCCUPANT LOAD OF |
| | THE STORY HAS INCREASED OVER 20%. REFER TO SEC. 810.1 |
| | FBC EX AND PROVIDE PLUMBING FIXTURE CALCULATIONS IN |
| | COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE |
| | THAT INDICATES THE REQUIRED AND PROVIDED NUMBER OF |
| | PLUMBING FIXTURES. PLEASE NOTE THAT DRINKING FOUNTAINS |
| | AND SERVICE SINKS ARE REQUIRED FOR B OCCUPANCIES. |
| | |
| | 2) G110, A300, & A600: SHOW THE CLEAR FLOOR SPACE |
| | APPROACH DIAGRAMS AND DIMENSIONS AT THE SINKS, |
| | DISHWASHER AND REFRIGERATOR- SECTIONS 305, 606.2, |
| | 804.6.3 & 804.6.6 FBC ACC. |
| | |
| | 3) A600 DETAILS 5 & 6: PLEASE INDICATE THE SINKS SHALL |
| | BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR |
| | COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOORS- SEC. 606.3 FBC ACC. |
| | |
| | 4) A600: THE CONTROLS AND HANDLE FOR THE MICROWAVE |
| | APPEAR TO BE ABOVE THE MAXIMUM REACH RANGES AS |
| | INDICATED IN SEC 308 FBC ACC. |
| | |
| | 5) A600: VERIFY THE FREEZER INSIDE THE REFRIGERATOR HAS |
| | A MINIMUM OF 50 PERCENT OF FREEZER SPACE 54-INCHES |
| | MAXIMUM FROM THE FINISHED FLOOR- SEC. 804.6.6 FBC ACC. |
| | |
| | 6) P-200: PLEASE SHOW THE LOCATIONS OF THE REQUIRED |
| | CHECK VALVES AND FULL OPEN VALVES ON THE PUMP DISCHARGE |
| | PIPES, AND SHOW HOW ACCESS TO THE VALVES WILL BE |
| | PROVIDED- SEC. 712.2 FBC P. |
| | |
| | 7) P-300: FULL OPEN DEDICATED VALVES ARE REQUIRED FOR |
| | THE COLD WATER SUPPLY LINES TO THE WATER HEATERS- SECS. |
| | 503.1 & 606.1 (8) FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |