| Plan Review Notes For Permit 21110232 |
| Permit Number |
21110232 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-12-20 14:38:40 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21110232 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-200: ASHRAE 62.1-1999 IS REFERENCED IN THE | | | VENTILATION RATES BOX. PLEASE REFERENCE THE CURRENT | | | ASHRAE 62.1-2013 EDITION OR THE FBC M 2017 EDITION. | | | | | | 2) PLEASE REFERENCE THE CURRENT EDITION OF 2020 FBC | | | MECHANICAL. | | | | | | 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS. FBC M | | | 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|