Plan Review Notes
Plan Review Notes For Permit 21110232
Permit Number 21110232
Review Stop B
Sequence Number 1
Notes
Date Text
2022-01-05 14:23:47WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21110232
 ADD: 218 DATURA ST. / 2ND FLOOR EXPANSION
 CONT: SIMON CONTRACTING SERVICES
 TEL: 561-371-5519
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 05TH/ 2022
 ACTION: DENIED
  
 1) SHEET A-600 DETAIL # 5 SHOWS THE SNACK ROOM
 COUNTERTOP AND SINK AT AN ELEVATION 3 FEET ABOVE FINISH
 FLOOR. PLEASE REFER TO THE 2020 FBC-ACCESSIBILITY CODE
 SECTION:
 606 LAVATORIES AND SINKS> 2020 FBC-ACCESSIBILITY CODE
 SECTION 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 2) SHEET A-600 IN DETAIL # 3THE CONFERENCE ROOM
 COUNTERTOP IS ALSO AT AN ELEVATION OF 3 FEET TO THE TOP
 OF THE COUNTERTOP. SEE 2020 FBC-ACCESSIBILITY CODE
 SECTION 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL
 BE 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 3) SHEET A-600 DETAIL # 5 SHOWS THE SNACK ROOM WITH
 MICROWAVE SHELF (BOTTOM OF SHELF) AT 4 FEET 6 INCHES
 ABOVE FINISH FLOOR. 2020 FBC-ACCESSIBILITY CODE
 SECTIONS:
  
 3A) 308 REACH RANGES.
 308.2 FORWARD REACH / 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 3B) 309 OPERABLE PARTS.
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM.
  
 4) SHEET A-300 & A-700 THE DOOR SCHEDULE SHOWS DOORS TO
 STAIRWELLS DOOR 200.1 EX. STAIR # 1 AND DOOR 210.1 TO
 EXIT STAIR # 2 THEY ARE EXISTING, BUT NO FIRE RATING IS
 PROVIDED. 2020 FBC-B TABLE 716.5.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  