| 2021-11-16 09:53:06 | 11/16/21 2ND LP GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE COPY OF THE TIE-DOWN IS NOT ACCEPTABLE. PLEASE |
| | DROP OFF THE ORIGINAL SIGNED AND SEALED DOCUMENT ALONG |
| | WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON |
| | FOR SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN |
| | REVIEW REQUEST FORM CAN BE OBTAINED BY EMAILING |
| | [email protected] AND ASKING FOR THE FORM. |
| | |
| | 2. WOULD YOU PLEASE SUBMIT THE CORRECT BTU LOAD ON THE |
| | SYSTEM. THE 355 BTU'S IS INCORRECT, AND THIS MAY BE |
| | REDLINED IF PERMISSION IS GIVEN PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 3. SHOW THE DEPTH OF THE LP GAS CONTAINER BELOW GRADE |
| | TO COMPLY WITH NFPA 58 SEC. 6.6.6.1. |
| | |
| | 4. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| | PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP |
| | CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. WOOULD YOU PLEASE SUBMIT DETAILS ON THE TYPE OF |
| | CATHODIC PROTECTION, SIZE (LBS.) & THE NUMBER OF |
| | MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE AMOUNT OF |
| | WATER TO ACTIVATE IT PER THE NFPA 58 SECS. 5.2.1.11, |
| | 6.6.6.1 (I). |
| | |
| | 6. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |