| 2022-01-25 09:37:28 | RESIDENTIAL(R3) WINDOW REPLACEMENT, BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT # |
| | |
| | NOTE: |
| | LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| | SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| | COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| | THE FLORIDA BUILDING CODE. |
| | |
| | 1- GRAY BEDROOM EMERGENCY EGRESS WINDOW COMPLIANCE IS |
| | NOT CLEAR. FLOOR PLAN SHOWS WINDOW #38 AS THE EGRESS |
| | WINDOW, BUT WINDOW/DOOR SCHEDULE SHOWS WINDOW #38 AS A |
| | "PICTURE WINDOW". A PICTURE WINDOW DOESN'T OPEN. IT |
| | DOESN'T COMPLY WITH EGRESS. REVISE/CLARIFY AS REQUIRED. |
| | ALSO, WINDOW/DOOR SCHEDULE IS MISSING WINDOW #15. |
| | |
| | 2- THIS HOUSE IS BUILT IN A ZERO LOT DEVELOPMENT. |
| | WINDOWS ARE NOT ALLOWED ON THE ZERO LOT LINE. SEC. |
| | R302.1 FBC-RESIDENTIAL. WINDOWS #10 THRU #13 CAN NOT BE |
| | INSTALLED. REVISE INFORMATION ON FLOOR PLAN, |
| | WINDOW/DOOR SCHEDULE AND ALL PRODUCT APPROVALS |
| | SUBMITTED AS REQUIRED. |
| | |
| | 3- SPECIFY SIZE AND TYPE OF EXISTING WINDOW AND SIZE |
| | AND TYPE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE WITH |
| | THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING |
| | BUILDING. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |