Plan Review Notes
Plan Review Notes For Permit 21110196
Permit Number 21110196
Review Stop B
Sequence Number 1
Notes
Date Text
2022-01-25 09:37:28RESIDENTIAL(R3) WINDOW REPLACEMENT, BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 1- GRAY BEDROOM EMERGENCY EGRESS WINDOW COMPLIANCE IS
 NOT CLEAR. FLOOR PLAN SHOWS WINDOW #38 AS THE EGRESS
 WINDOW, BUT WINDOW/DOOR SCHEDULE SHOWS WINDOW #38 AS A
 "PICTURE WINDOW". A PICTURE WINDOW DOESN'T OPEN. IT
 DOESN'T COMPLY WITH EGRESS. REVISE/CLARIFY AS REQUIRED.
 ALSO, WINDOW/DOOR SCHEDULE IS MISSING WINDOW #15.
  
 2- THIS HOUSE IS BUILT IN A ZERO LOT DEVELOPMENT.
 WINDOWS ARE NOT ALLOWED ON THE ZERO LOT LINE. SEC.
 R302.1 FBC-RESIDENTIAL. WINDOWS #10 THRU #13 CAN NOT BE
 INSTALLED. REVISE INFORMATION ON FLOOR PLAN,
 WINDOW/DOOR SCHEDULE AND ALL PRODUCT APPROVALS
 SUBMITTED AS REQUIRED.
  
 3- SPECIFY SIZE AND TYPE OF EXISTING WINDOW AND SIZE
 AND TYPE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE WITH
 THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING
 BUILDING.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]