2022-04-12 16:12:41SECOND BUILDING AUDIT FOR PERMIT #21110176
 PRIVATE PROVIDER
 SEC. 553.791 F.S.
  
 NEW SINGLE FAMILY RESIDENCE
 CODE IN EFFECT: FBC-RESIDENTIAL,7TH EDITION, 2020.
  
 ORIGINAL COMMENT:
 1- ROOF SHEATHING NAILING SPACING SPECIFIED ON SHEET
 S-2 DOESN'T COMPLY WITH TABLE R803.2.3.1
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 RESPONSE:
 (A)REPEAT COMMENT. ROOF SHEATHING NAILING SPACING
 SPECIFICATIONS SHOWN ON THE RIGHT HAND SIDE OF ROOF
 DIAGRAMS STILL DON'T COMPLY WITH TABLE R803.2.3.1
 FBC-RESIDENTIAL. SEE TABLE AND REVISE AS REQUIRED.
  
 (B)ROOF SHEATHING NAILING SPACING SPECIFICATIONS SHOWN
 ON THE RIGHT HAND SIDE OF ROOF DIAGRAMS IS MISSING ROOF
 ZONE 2N.
 SEC. R803.2.3.1 FBC-RESIDENTIAL.
  
 (C)ROOF SHEATHING NAILING SPACING SPECIFICATIONS SHOWN
 ON THE RIGHT HAND SIDE OF ROOF DIAGRAMS ARE SHOWING TWO
 DIFFERENT NAILING SPACING SPECIFICATIONS FOR ROOF ZONE
 2E AND 2R. THIS IS NO CLEAR. PROVIDE ONLY ONE NAILING
 SPECIFICATION TO AVOID CONFLICTS. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 2- OK.
 3- OK.
 4- OK.
  
 ORIGINAL COMMENT:
 5- WIND DESIGN INFORMATION ON SHEET A-1 IS NOT CLEAR.
 ULTIMATE WIND SPEED AND NOMINAL WIND SPEED UNDER WALL
 PRESSURES DON'T MATCH THE ULTIMATE WIND SPEED AND
 NOMINAL WIND SPEED UNDER WIND DESIGN BASIS SHOWN ON THE
 SAME SHEET. REVISE/CLARIFY AS REQUIRED. WHICH ONE IS
 THE CORRECT DESIGN CRITERIA FOR THIS HOUSE? SEC.
 R301.2.1 FBC-RESIDENTIAL.
 NOTE: REVISE WINDOWS/DOORS DESIGN PRESSURES ACCORDINGLY
 TO AVOID CONFLICTS/DELAYS.
  
 RESPONSE:
 ONE OF THE WINDOWS "C" ON BEDROOM #2 IS LOCATED IN ZONE
 5. THEREFORE, THE DESIGN PRESSURES FOR THIS WINDOW IS
 INCORRECT AS SPECIFIED ON THE WINDOW SCHEDULE AND
 PRODUCT APPROVAL SUBMITTAL AFFIDAVIT UNDER "DESIGN
 PRESSURES". REVISE AS REQUIRED.
  
 6- ENERGY CALCULATIONS:
 A)OK.
  
 ORIGINAL COMMENT:
 B)DOOR INFORMATION SPECIFIED ON PAGE 3 DOESN'T MATCH
 PLANS AND PRODUCT APPROVALS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION. REVISE AS REQUIRED. THERE IS
 NOT INSULATED DOOR ON THE SOUTH SIDE. THIS IS A
 METAL/GLASS FRENCH DOOR. NOTE: GLAZING IN DOORS NEEDS
 TO BE INCLUDED IN THE WINDOW GLAZING AREA. SEE SEC.
 R405.5.3 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. DOOR ON THE SOUTH SIDE WAS CHANGED TO
 WOOD. PLANS AND PRODUCT APPROVAL SUBMITTED DON'T
 SPECIFY WOOD DOOR. REVISE AS REQUIRED.
 NOTE: A METAL DOOR (2.67'X 8.0') WAS ADDED TO THE
 WINDOW LIST, THEN IT IS NOT CLEAR WHERE IS THE WOOD
 DOOR LOCATED AT. PLEASE CHECK, REVISE AS REQUIRED TO
 AVOID CONFLICTS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 ORIGINAL COMMENT:
 C)WINDOW OVERHANG DEPTH AND SEPARATION INFORMATION
 SHOWN ON PAGE 3 DOESN'T MATCH PLANS. SEC. R101.5.1.1.2
 FBC-. ENERGY CONSERVATION. REVISE AS REQUIRED TO MATCH.
  
 RESPONSE:
 REPEAT COMMENT. WINDOW OVERHANG DEPTH AND SEPARATION
 INFORMATION DOESN'T MATCH PLANS. SEE FRONT ELEVATION
 AND REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 D)WINDOW AREA SHOWN ON PAGE 3 DOESN'T MATCH PLANS. SEC.
 R101.5.1.1.2 FBC-. ENERGY CONSERVATION. REVISE AS
 REQUIRED TO MATCH.
  
 RESPONSE:
 REPEAT COMMENT. WINDOW AREA FOR BEDROOM #2 DOESN'T
 MATCH PLANS. REVISE AS REQUIRED TO MATCH.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER