| Plan Review Notes For Permit 21110174 |
| Permit Number |
21110174 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-12-10 11:00:46 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1, THE PLANS DO NOT SHOW THE DESIGN WIND | | | SPEED AND THE ENGINEER'S LETTER INDICATES A DESIGN WIND | | | SPEED OF 150 MPH. THIS SHOULD BE 170 MPH. |
|