2021-11-22 06:50:561ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21110169
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC R403.7.1
  
 2) PLEASE PROVIDE INFORMATION ON THE KITCHEN HOOD, WHAT
 IS THE CFM?S OF EXHAUST FOR THIS HOOD? IS MAKE UP AIR
 REQUIRED? FBC RES M1503.4
  
 3) PLEASE SHOW THE RETURN AIR PATH FROM THE BEDROOMS
 BACK TO THE AHU. PLEASE ALSO EXPLAIN HOW THE RETURN AIR
 WILL REACH THE AHU WITH THE AHU CLOSET DOOR CLOSED. FBC
 RES M1602.3
  
 4) PLEASE SHOW THE CONDENSATE DRAIN LINE AND THE
 TERMINATION LOCATION. FBC RES M1411.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  