| 2022-03-02 12:11:17 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21110157 |
| | 3/2/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITONAL NOTES. |
| | PLEASE COMPLY WITH THE COMMENTS AND NOTES. |
| | |
| | 4) FAILED. P1.1 & P2.1: THE CLEAR WATER WASTE FROM THE |
| | HAND SINK, WALK-IN COOLER EVAPORATOR AND THE ICE |
| | MACHINE SHALL NOT DRAIN INTO THE GREASE WASTE LINE AND |
| | INTERCEPTOR- SECTION 1003.3.1 FBC P. THE CONDENSATE |
| | FROM THE EVAPORATOR IS ALSO RESTRICTED FROM DRAINING |
| | INTO THE SANITARY SYSTEM AND SHALL BE DISCHARGED TO AN |
| | APPROVED LOCATION SUCH AS THE STORM DRAIN SYSTEM OR |
| | DRYWELL- SEC. 90-126 WPB CODE OF ORDINANCES. PLAN AND |
| | RISER NOT CORRECTED. |
| | |
| | 5) FAILED P1.1 & P2.1: SHOW DRAINAGE AND VENT PIPING |
| | FOR THE UNDERCOUNTER DISHWASHER- SECTION 1003.3.1 FBC |
| | P. FLOOR SINK NOT VENTED- SEE SECS. 910.1, 911.1, |
| | 915.1, AND TABLE 909.1 FBC P. PLAN AND RISER ALSO DO |
| | NOT PROVIDE THE DRAIN PIPE SIZE (DIAMETER). |
| | |
| | 7) FAILED. P1.1 & P2.1: SHOW THE LOCATIONS OF REQUIRED |
| | BACKFLOW PREVENTERS FOR WATER LINE CONNECTIONS TO THE |
| | DISHWASHERS, BEVERAGE DISPENSERS, COFFEE BREWER, |
| | EXPRESSO MACHINE, WATER FILTER ETC.- SECTION 608.3 FBC |
| | P. PLEASE INCLUDE A DEVICE SCHEDULE INDICATING MAKES, |
| | MODELS AND COMPLIANCE STANDARDS. THE BACKFLOW |
| | PREVENTERS SHALL BE INSTALLED INDIVIDUALLY ON THE |
| | SUPPLY LINES TO THE COFFEE MAKER AND EXPRESSO MACHINE- |
| | SEC. 608.3 FBC P. |
| | |
| | 12) FAILED. ENERGYGAUGE COMPLIANCE FORM: INCORRECT |
| | COMPLIANCE DATA FOR THE WATER HEATER AND WATER PIPING |
| | HAS BEEN ENTERED. THE WATER HEATER IS GAS, NOT |
| | ELECTRIC, HW TEMPERATURE IS HIGHER THAN 105 DEGREES F, |
| | PIPING IS LARGER THAN 0.25. PLEASE SEE SECTION C404.1 |
| | FBC EC. FORM NOT CORRECTED. |
| | |
| | NEW COMMENTS: |
| | |
| | 1) SHEETS P1.1 & P1.2: REFER TO SEC. 607.1.1 FBCP AND |
| | PROVIDE EITHER A MASTER THERMOSTATIC MIXING VALVE AT |
| | THE WATER HEATER OR INDIVIDUAL MIXING VALVES AT |
| | FIXTURES SUPPLYING HOT WATER INCLUDING THE HAND SINKS, |
| | MOP SINKS, AND 3-COMPARTMENT SINKS. PLEASE NOTE THE |
| | LAVATORY SINKS ARE APPROVED FOR DELIVERY OF TEMPERED |
| | WATER USING THE ASSE 1070 MIXING VALVES. |
| | |
| | 2) P1.1: MAKES AND MODELS FOR THE FOOD EQUIPMENT |
| | FIXTURES AND APPLIANCES HAVE NOT BEEN PROVIDED. IN |
| | ACCORDANCE WITH SEC. 107.4.1 WPB. PLEASE NOTE THOSE |
| | ITEMS AS DEFERRED SUBMITTALS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |