| 2022-03-02 12:29:46 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21110157 |
| | 3/2/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISRTED BELOW WITH ADDITIONAL NOTES. |
| | PLEASE COMPLY WITH THE COMMENTS AND NOTES. |
| | |
| | 4) FAILED. P2.1: SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR THE REGULATORS, THE COOKING APPLIANCES, AND THE GAS |
| | WATER HEATER- SECTIONS 410.2, 623.1, AND 624.1 FBC FG. |
| | THE RANGE SUBMITTAL INDICATES THE APPLIANCE HAS A |
| | 280,000 BTU LOAD HOWEVER THE RISER INDICATES 70,000 |
| | BTU. PLEASE CORRECT THE RISER DRAWING ACCORDINGLY. |
| | |
| | 5) FAILED. P2.1: PROVIDE COMBUSTION AIR CALCULATIONS |
| | FOR THE COOKING APPLIANCES AND INDICATE HOW THE AIR |
| | WILL BE SUPPLIED- SECTION 304.1 FBC FG. NOT PROVIDED. |
| | THE NARRATIVE RESPONSE REFERENCES THE CAPTIVE AIRE |
| | DRAWINGS HOWEVER MAKE-UP AIR FOR HOOD EEXHAUST IS NOT |
| | COMBUSTION AIR FOR APPLLIANCES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |