| 2021-11-30 13:47:55 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21101057 |
| | 11/30/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A1.00 & P0.1: PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS FOR THE NEW RESTAURANT IN COMPLIANCE WITH |
| | TABLE 403.1 FBC P. PROVIDE A SCHEDULE THAT INDICATES |
| | THE REQUIRED AND PROVIDED NUMBER OF PLUMBING FIXTURES. |
| | BASED ON THE TABLE AND THE OCCUPANT LOAD OF 240 |
| | PERSONS, THE PLANS APPEAR TO SHOW A DEFICIENCY OF 1 |
| | MALE WATER CLOSET AND 1 FEMALE WATER CLOSET. PLEASE |
| | NOTE DRINKING FOUNTAINS ARE REQUIRED FIXTURES FOR |
| | RESTAURANTS UNLESS WATER WILL BE SERVED IN CONTAINERS |
| | FREE OF CHARGE IN ACCORDANCE WITH SECTION 410.4 FBC P. |
| | PLEASE REVISE THE PLANS TO INDICATE WHICH METHOD WILL |
| | BE USED AND ALSO TO SHOW THE ADDITION MALE AND FEMALE |
| | WATER CLOSETS- SECTION 107.2.1 WPB. |
| | |
| | 2) A3.00: FBC- 2020 ACCESSIBILITY COMPLIANCES: |
| | A) DIMENSIONS OF THE CLEAR FLOOR SPACE DIAGRAMS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | B) DIMENSIONS OF THE CLEAR FLOOR SPACE DIAGRAMS FOR THE |
| | LAVATORIES- 606.2. |
| | C) TURNING SPACE DIAMETERS- 304.3. |
| | D) DIMENSIONS OF THE CLEAR FLOOR SPACE DIAGRAM BEYOND |
| | THE ARC OF THE DOOR- 603.2.3 |
| | E) HEIGHTS OF THE WATER CLOSET SEATS (NOT THE RIMS OF |
| | THE BOWLS) FROM THE FINISHED FLOORS- SECTION 604.4. |
| | F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- 603.3. THE DETAIL SHOWS THE |
| | MEASUREMENT TO THE BOTTOM OF MIRROR FRAME. |
| | G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF THE GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. ADD A NOTE TO THE SIDE BAR |
| | GRAB BAR TO INDICATE IT SHALL EXTEND A MINIMUM OF 54 |
| | INCHES FROM THE REAR WALL. SHOW THE REAR GRAB WILL |
| | EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 |
| | INCHES TOWARDS THE SIDE WALL AND 24 INCHES ON THE OTHER |
| | SIDE. |
| | H) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- 604.6. |
| | I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- 606.2 |
| | AND FIGURES 306.2 & 306.3. |
| | |
| | 2) A3.00: PLEASE INDICATE THE WALL SURROUND FINISH |
| | MATERIALS TO BE INSTALLED IN THE BATHROOMS AND AT THE |
| | MOP SINK- SECTION 310.3 FBC P AND 1210.2.2 FBC B- WALLS |
| | AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS |
| | AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF |
| | A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 3) P0.1 & A1.01: THE GREASE INTERCEPTOR CALCULATIONS ON |
| | P0.1 INDICATE 70 SEATS HOWEVER 160 SEATS ARE INDICATED |
| | ON A1.01. PLEASE REVISE THE CALCULATIONS- SECTION |
| | 1003.3 FBC P. BASED ON THE FORMULA USED THE REQUIRED |
| | INTERCEPTOR CAPACITY IS 1920 GALLONS. SPECIFICATIONS |
| | FOR THE GB-250 INDICATE THE INTERCEPTORS ARE UNDERSIZED |
| | FOR THE LOAD- GREASE RETENTION CAPACITY IS BASED ON |
| | 100/200 GPM FLOW WITH 200 GPM BEING THE MAXIMUM OF EACH |
| | OF THE 3 INTERCEPTORS. |
| | |
| | 4) P1.1 & P2.1: THE CLEAR WATER WASTE FROM THE HAND |
| | SINK, WALK-IN COOLER EVAPORATOR AND THE ICE MACHINE |
| | SHALL NOT DRAIN INTO THE GREASE WASTE LINE AND |
| | INTERCEPTOR- SECTION 1003.3.1 FBC P. THE CONDENSATE |
| | FROM THE EVAPORATOR IS ALSO RESTRICTED FROM DRAINING |
| | INTO THE SANITARY SYSTEM AND SHALL BE DISCHARGED TO AN |
| | APPROVED LOCATION SUCH AS THE STORM DRAIN SYSTEM OR |
| | DRYWELL- SEC. 90-126 WPB CODE OF ORDINANCES. |
| | |
| | 5) P1.1 & P2.1: SHOW DRAINAGE AND VENT PIPING FOR THE |
| | UNDERCOUNTER DISHWASHER- SECTION 1003.3.1 FBC P. |
| | |
| | 6) P1.1 & P2.1: SHOW THE WATER LINE CONNECTIONS TO THE |
| | UNDERCOUNTER DISHWASHER, BEVERAGE DISPENSERS, COFFEE |
| | BREWER, EXPRESSO MACHINE ETC.- SECTION 107.2.1 WPB. |
| | CLARIFY IF A WATER FILTERING SYSTEM WILL BE INSTALLED |
| | AND ADD IT TO THE DRAWINGS AND EQUIPMENT SCHEDULE IF |
| | APPLICABLE. |
| | |
| | 7) P1.1 & P2.1: SHOW THE LOCATIONS OF REQUIRED BACKFLOW |
| | PREVENTERS FOR WATER LINE CONNECTIONS TO THE |
| | DISHWASHERS, BEVERAGE DISPENSERS, COFFEE BREWER, |
| | EXPRESSO MACHINE, WATER FILTER ETC.- SECTION 608.3 FBC |
| | P. PLEASE INCLUDE A DEVICE SCHEDULE INDICATING MAKES, |
| | MODELS AND COMPLIANCE STANDARDS. |
| | |
| | 8) P120: PROVIDE WATER HAMMER ARRESTOR SYMBOLS ON THE |
| | WATER ISOMETRIC DRAWING- SECTION 604.9 FBC P. |
| | |
| | 9) P120: PROVIDE AN ENLARGED WATER FILTER PIPING |
| | DRAWING (IF INSTALLED) INDICATING COMPLIANCE WITH |
| | SECTIONS 608.3 & 608.4 FBC P. |
| | |
| | 10) P120: THE PLAN SHOWS NON-COMPLIANCE WITH SECTION & |
| | TABLE C404.5.1 FBC EC. A 1/2 INCH HW PIPE HAS A MAXIMUM |
| | ALLOWABLE LENGTH OF 2 FT. FROM THE NEAREST HOT WATER |
| | SOURCE TO THE FIXTURE SUPPLY PIPE AT THE LAVATORIES. |
| | PLEASE PROVIDE EITHER POINT OF USE WATER HEATERS AT THE |
| | LAVATORIES OR A HOT WATER RECIRCULATION PUMP. |
| | |
| | 11) P0.1: PLEASE PROVIDE A PLUMBING FIXTURE SCHEDULE OR |
| | INDICATE WHICH FIXTURES WILL BE DEFERRED SUBMITTALS- |
| | SECTION 107.1 & 107.3.4.1 WPB. CLARIFY IF THE WATER |
| | CLOSETS WILL BE FLUSH TANKS OR FLUSH VALVES- SEE TABLE |
| | 604.3 FBC P. |
| | |
| | 12) ENERGYGAUGE COMPLIANCE FORM: INCORRECT COMPLIANCE |
| | DATA FOR THE WATER HEATER AND WATER PIPING HAS BEEN |
| | ENTERED. THE WATER HEATER IS GAS, NOT ELECTRIC, HW |
| | TEMPERATURE IS HIGHER THAN 105 DEGREES F, PIPING IS |
| | LARGER THAN 0.25. PLEASE SEE SECTION C404.1 FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |