| Plan Review Notes For Permit 21110153 |
| Permit Number |
21110153 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-01-26 08:09:23 | WED.JAN. 26TH/ 2022 | | | ACTION: PASSED/ BUILDING PROVISO | | | | | | BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS. NEW | | | ROOF TOP FRAMING FOR NEW ROOF TOP UNIT. | | | THIS BUILDING CONTAINS EITHER BOLTED AND OR WELDED | | | CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD | | | PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE | | | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED | | | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON | | | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL | | | BE REQUIRED. | | | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO | | | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS | | | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING | | | INSPECTION. | | | 2020 FBC-B 2204.1 WELDING | | | 1. WELD PROCEDURES SPECIFICATIONS | | | 2. QUALIFICATIONS OF WELDING PERSONAL | | | 2017 FBC-B 2204.2 BOLTING. | | | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, | | | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD | | | AT 561-805-6666 OR ACTING CHIEF BUILDING INSPECTOR | | | RICHARD BRUNELLE AT 561-805-6670. | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | |
|