| Date |
Text |
| 2021-12-14 20:39:30 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21110145 |
| | 12/14/2021 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| | EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1. PLEASE GIVE DIMENSIONS FOR FIXTURE CLEARANCES PER |
| | FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY |
| | CODE.WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. FBC P- 410.3 PROVIDE HIGH AND LOW DRINKING |
| | FOUNTAINS. |
| | WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN |
| | TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE |
| | WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL |
| | COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS. |
| | FBC P- 410.4SUBSTITUTION. |
| | WHERE RESTAURANTS PROVIDE DRINKING WATER IN A CONTAINER |
| | FREE OF CHARGE, DRINKING FOUNTAINS SHALL NOT BE |
| | REQUIRED IN THOSE RESTAURANTS. IN OTHER OCCUPANCIES |
| | WHERE DRINKING FOUNTAINS ARE REQUIRED, WATER DISPENSERS |
| | SHALL BE PERMITTED TO BE SUBSTITUTED FOR NOT MORE THAN |
| | 50 PERCENT OF THE REQUIRED NUMBER OF DRINKING |
| | FOUNTAINS. |
| | |
| | 3. PLEASE SHOW ALL OF THE INTERIOR DIMENSIONS OF THE |
| | RESTROOMS AND TO INCLUDE TURNING RADIUS.WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 4. PLEASE PROVIDE RESTROOM FIXTURE ELEVATIONS CLEARLY |
| | SHOWING ALL MEASUREMENTS TO BE IN COMPLIANCE WITH FBC |
| | ACCESSIBILITY 2020 |
| | |
| | 5. PLEASE PROVIDE DIRECTIONAL SIGNAGE AS PER |
| | FBC-P403.4.1 DIRECTIONAL SIGNAGE INDICATING THE ROUTE |
| | TO THE REQUIRED PUBLIC TOILET FACILITIES SHALL BE |
| | POSTED IN A LOBBY, CORRIDOR, AISLE OR SIMILAR SPACE, |
| | SUCH THAT THE SIGN CAN BE READILY SEEN FROM THE MAIN |
| | ENTRANCE TO THE BUILDING |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |