| 2021-12-23 16:17:31 | HALFWAY HOUSE |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE A SURVEY SHOWING THE BUILDING |
| | LOCATION AND FLOOD ZONE. |
| | |
| | 2) PLEASE SHOW THE RESTROOM AND MOP SINK AREA WALL |
| | FINISHES FBC 1210.2.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, |
| | |
| | 3) PLEASE SHOW THE ACCESSIBLE ROUTE TO THE BUILDING FBC |
| | 206.2.2 WITHIN A SITE. |
| | AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE |
| | BUILDINGS, ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, |
| | AND ACCESSIBLE SPACES THAT ARE ON THE SAME SITE. |
| | |
| | 4) ACCESSIBLE RESTROOM - DOORS SHALL NOT SWING INTO THE |
| | FIXTURE CLEAR FLOOR SPACE - 603.2.3 DOOR SWING. |
| | DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR |
| | CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE |
| | PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE. |
| | EXCEPTIONS:2.WHERE THE TOILET ROOM OR BATHING ROOM IS |
| | FOR INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING |
| | WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC |
| | OF THE DOOR SWING, DOORS SHALL BE PERMITTED TO SWING |
| | INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR |
| | ANY FIXTURE. (FOR THE EXCEPTION - PLEASE SHOW THE CLEAR |
| | FLOOR SPACE) |
| | |