| 2022-01-18 13:15:48 | ELECTRICAL AUDIT |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2020 7TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| | NFPA 70 2017 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PAGE E-201 |
| | |
| | CONFERENCE ROOMS 11-05, AND 11-18 NEED WALL OUTLETS |
| | INSTALLED PER 210.71(B)(1) |
| | |
| | 210.71 MEETING ROOMS. |
| | (A) GENERAL. EACH MEETING ROOM OF NOT MORE THAN 93 M2 |
| | (1000 FT2) IN OTHER THAN DWELLING UNITS SHALL HAVE |
| | OUTLETS FOR |
| | NONLOCKING-TYPE, 125-VOLT, 15- OR 20-AMPERE |
| | RECEPTACLES. THE OUTLETS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH 210.71(B). WHERE |
| | A ROOM OR SPACE IS PROVIDED WITH MOVABLE PARTITION(S), |
| | EACH ROOM SIZE SHALL BE DETERMINED WITH THE PARTITION |
| | IN THE POSITION |
| | THAT RESULTS IN THE SMALLEST SIZE MEETING ROOM. |
| | (B) RECEPTACLE OUTLETS REQUIRED. THE TOTAL NUMBER OF |
| | RECEPTACLE OUTLETS, INCLUDING FLOOR OUTLETS AND |
| | RECEPTACLE OUTLETS IN |
| | FIXED FURNITURE, SHALL NOT BE LESS THAN AS DETERMINED |
| | IN (1) AND (2). THESE RECEPTACLE OUTLETS SHALL BE |
| | PERMITTED TO BE LOCATED AS |
| | DETERMINED BY THE DESIGNER OR BUILDING OWNER. |
| | (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE |
| | OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH |
| | 210.52(A)(1) THROUGH (A)(4). |
| | (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT |
| | LEAST 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF |
| | AT LEAST 20 M2 |
| | (215 FT2) SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET |
| | LOCATED IN THE FLOOR AT A DISTANCE NOT LESS THAN 1.8 M |
| | (6 FT) FROM ANY FIXED WALL |
| | FOR EACH 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR |
| | SPACE. |