2022-01-18 13:15:48ELECTRICAL AUDIT
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-201
  
 CONFERENCE ROOMS 11-05, AND 11-18 NEED WALL OUTLETS
 INSTALLED PER 210.71(B)(1)
  
 210.71 MEETING ROOMS.
 (A) GENERAL. EACH MEETING ROOM OF NOT MORE THAN 93 M2
 (1000 FT2) IN OTHER THAN DWELLING UNITS SHALL HAVE
 OUTLETS FOR
 NONLOCKING-TYPE, 125-VOLT, 15- OR 20-AMPERE
 RECEPTACLES. THE OUTLETS SHALL BE INSTALLED IN
 ACCORDANCE WITH 210.71(B). WHERE
 A ROOM OR SPACE IS PROVIDED WITH MOVABLE PARTITION(S),
 EACH ROOM SIZE SHALL BE DETERMINED WITH THE PARTITION
 IN THE POSITION
 THAT RESULTS IN THE SMALLEST SIZE MEETING ROOM.
 (B) RECEPTACLE OUTLETS REQUIRED. THE TOTAL NUMBER OF
 RECEPTACLE OUTLETS, INCLUDING FLOOR OUTLETS AND
 RECEPTACLE OUTLETS IN
 FIXED FURNITURE, SHALL NOT BE LESS THAN AS DETERMINED
 IN (1) AND (2). THESE RECEPTACLE OUTLETS SHALL BE
 PERMITTED TO BE LOCATED AS
 DETERMINED BY THE DESIGNER OR BUILDING OWNER.
 (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE
 OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH
 210.52(A)(1) THROUGH (A)(4).
 (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT
 LEAST 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF
 AT LEAST 20 M2
 (215 FT2) SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 LOCATED IN THE FLOOR AT A DISTANCE NOT LESS THAN 1.8 M
 (6 FT) FROM ANY FIXED WALL
 FOR EACH 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR
 SPACE.