| Plan Review Notes For Permit 21110142 |
| Permit Number |
21110142 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-18 15:33:08 | OFFICE BUILDOUT (PP AUDIT) | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING A8-1 SHOWS WOOD FRAMING AS FIRE RATED - | | | SHOULD BE NOTED AS FIRE RETARDANT TREATED PER FBC 603.1 | | | ALLOWABLE MATERIALS. (1).FIRE-RETARDANT-TREATED WOOD | | | | | | 2) DRAWING A8-11 AND A8-12 SHOWS PLYWOOD USED IN A DROP | | | CEILING - MATERIALS SHOULD BE NON CUMBUSTIBLE PER FBC | | | 803.13.2.1 | | | | | | 3) ACCESSIBLE RESTROOM - DRAWING A7-4 SHOWS A CABINET | | | (ACS-04) ABOVE THE TOILET GRAB BAR - PLEASE SHOW THE | | | REQUIRED 12 INCH CLEARANCE ABOVE THE GRAB BAR PER FBC | | | 609.3 "THE SPACE BETWEEN THE GRAB BAR AND PROJECTING | | | OBJECTS ABOVE SHALL BE 12 INCHES (305 MM) MINIMUM." |
|