Plan Review Notes
Plan Review Notes For Permit 21110113
Permit Number 21110113
Review Stop M
Sequence Number 1
Notes
Date Text
2021-12-07 16:58:23PLEASE PROVIDE A CLEARER DETAIL OF THE HOOD PENETRATING
 THE ROOF. IT APPEARS THAT THE ENTIRE ROOF HAS BEEN
 REMOVED AND THERE IS SOME TYPE OF COVER WRAPPING THE
 GREASE DUCT AND THE MAKE UP AIR DUCT. PLEASE SHOW THE
 DISTANCE FROM PARAPET TO GREASE DUCT, ALSO SHOW
 DISTANCE FROM TOP OF PARAPET TO THE GREASE DUT
 TERMINATION. SHOW THAT THE TERMINATION LOCATION OF
 GREASE DUCT MEETS THE REQUIREMENTS FROM NEIGHBORING
 BUILDINGS. FBC M 506.3.13.3 EXCEPTION.
  