| Plan Review Notes For Permit 21110113 |
| Permit Number |
21110113 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-12-07 16:58:23 | PLEASE PROVIDE A CLEARER DETAIL OF THE HOOD PENETRATING | | | THE ROOF. IT APPEARS THAT THE ENTIRE ROOF HAS BEEN | | | REMOVED AND THERE IS SOME TYPE OF COVER WRAPPING THE | | | GREASE DUCT AND THE MAKE UP AIR DUCT. PLEASE SHOW THE | | | DISTANCE FROM PARAPET TO GREASE DUCT, ALSO SHOW | | | DISTANCE FROM TOP OF PARAPET TO THE GREASE DUT | | | TERMINATION. SHOW THAT THE TERMINATION LOCATION OF | | | GREASE DUCT MEETS THE REQUIREMENTS FROM NEIGHBORING | | | BUILDINGS. FBC M 506.3.13.3 EXCEPTION. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|