| Plan Review Notes For Permit 21110113 |
| Permit Number |
21110113 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-12-03 11:24:34 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION OF A TYPICAL ROOF SECTION | | | THAT MAY NOT BE A TRUE REPRESENTATIVE OF THE "ACTUAL" | | | SITE INSTALLTION AND DIMENSIONS. | | | | | | PLEASE PROVIDE GREATER DETAIL AND DIMENSIONS FROM ALL | | | COMBUSTILE STRUCTURE INCLUDING THE PARAPIT WALL, | | | EXHAUST TOCLEAR AIR INTAKE AND EXHAUST TO OTHER INTAKES | | | AND OPENINGS. | | | | | | ENSURE ACTUAL DIMENSIONS MEET THE MINIMUM REQUIRMENTS | | | PER NFPA 96. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|