| 2021-11-10 08:19:05 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 21110108 |
| | W. P. B. PERMIT: 21070067 |
| | ADD: 1801 N. FLAGLER DR. # 210 |
| | CONT: LOWES HOME CENTER |
| | TEL: 561-771-0047 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW/ REVISION |
| | DATE: WED. NOV. 07TH/ 2021 |
| | ACTION: DENIED |
| | |
| | 1) THIS REVISION STATES, CONTRACT AMENDMENT, NEW FLOOR |
| | PLAN, UNDERLAYMENT SPECS. THE TERM UNDERLAYMENT FOR NEW |
| | REPLACEMENT FLOORS, TILE REQUIRES 3 SEPARATE TEST TO BE |
| | SUBMITTED. SEE COMMENTS 1A, 1B, & 1C FOR REQUIRED TEST. |
| | INSTALLATION DESCRIPTION PAGE 2 OF 9 LIST ALL ELEMENTS |
| | TO BE INSTALLED AND THERE IS NO SOUND ABATEMENT TESTING |
| | REPORTS FOR UNDERLAYMENT ON A 6 INCH CONCRETE SLAB. THE |
| | ORIGINAL PERMIT 21070067 LISTED PROFLEX SUPER SIM 90 AS |
| | THE APPROVED UNDERLAYMENT. |
| | |
| | 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 1C) FBC-B-2017 720.2 CONCEALED INSTALLATION. INSULATING |
| | MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF |
| | ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD |
| | INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX |
| | OF NOT MORE THAN 450. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 2) THE SUBMITTED FLOOR PLAN 002 WAS COPIED IN LANDSCAPE |
| | MODE AND CUT THROUGH THE GUEST BATH DRAWING, INCOMPLETE |
| | DRAWING. 107.2.1.3. QUALITY OF PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A 1/8TH INCH SCALE ON SUBSTANTIAL |
| | PAPER. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENT POLICY OTHER STANDARDS FOR THE PLANS AND |
| | SPECIFICATIONS IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORD MANAGEMENT. ELECTRONIC |
| | MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS |
| | OF FLORIDA STATUTES. |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |