Plan Review Notes
Plan Review Notes For Permit 21110081
Permit Number 21110081
Review Stop P
Sequence Number 1
Notes
Date Text
2021-12-14 09:43:2312/14/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET M-400;
  
 A. UNCONTAMINATED COOLING WATER OR AIR CONDITIONING
 CONDENSATE SHALL NOT DISCHARGE TO THE SANITARY SYSTEM
 UNLESS SPECIFICALLY AUTHORIZED BY THE CITY N WRITING
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES CHAPTER
 90, ARTICLE III, SEC. 90-126 (B) (5).
  
 B. A DRY WELL IS AN OPTION OR ROUTE TO A SAFE LOCATION.
 SUBMIT A DETAIL OF THE DRYWELL FOR THE CONDENSATE LINE
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. ON SHEET P-101, UNDER THE SCOPE OF WORK FOR A, WE DO
 NOT USE THE PALM BEACH COUNTY AMENDMENT; PLEASE CHANGE
 TO THE WEST PALM BEACH AMENDMENTS TO FBC.
  
 3. PLEASE NOTE THAT UPDATED VERSION A REVISIONS ARE ON
 FILE IN CITY RECORDS. THE ONES SUBMITTED WILL NEED TO
 BE THE NEW UPDATED REVISION PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  