| Plan Review Notes For Permit 21110081 |
| Permit Number |
21110081 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-10 11:49:01 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS AN INDICATION OF A WALK-IN COOLER; HOWEVER, | | | THE LOCATION OF THE COOLER WITHIN THE OCCUPANCY IS | | | UNCLEAR. | | | | | | PLEASE PROVIDE THE SPECIFIC COOLER LOCATION ON THE | | | FLOOR PLAN. | | | | | | 2) THERE IS AN INDICATION OF A FIRE SPRINKLER PALN; | | | HOWEVER, IT IS UNCLEAR IF THE COOLER IS PROTECTED BY A | | | REQUIRED SPRINKLER HEAD(S). | | | | | | PLEASE PROVIDE THE AN INDICATION OF A SPRINKLER HEAD(S) | | | WITHIN THE COOLER. | | | | | | | | | 3) THERE IS NO INDICATION OF AN EMERGENCY LIGHT WITHIN | | | THE COOLER. | | | | | | PLEASE PROVIDE DETAILS IF THE OCCUPANCY WERE TO LOSE | | | POWER AND THE ILLUMINATION OF THE EXIT OUT OF THE | | | COOLER OR PROVIDE AN EMERGENCY LIGHT. | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|