| 2022-05-16 13:25:11 | RESIDENTIAL (R3) ALTERATION THIRD BUILDING AUDIT. |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21110017 (GUEST HOUSE) |
| | |
| | NOTE: |
| | THIS IS A LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING |
| | BUILDING. SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3 |
| | FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| | |
| | 1- OK. |
| | 2- OK. |
| | |
| | ORIGINAL COMMENT: |
| | 3- SECOND FLOOR BEDROOM EGRESS WINDOWS DON'T SEEM |
| | COMPLY WITH SEC. R310.2.1 FBC-RESIDENTIAL. REVISE AS |
| | REQUIRED. SHOW COMPLIANCE WITH MIN. CLEAR OPENINGS |
| | (WIDTH, HEIGHT AND TOTAL CLEAR OPENING). |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | UNABLE TO VERIFY EGRESS WINDOW. |
| | |
| | ORIGINAL COMMENT: |
| | 4- PLANS DON'T PROVIDE ANY INFORMATION ABOUT SECOND |
| | FLOOR WINDOW FALL PROTECTION. WINDOW FALL PROTECTION |
| | SHALL BE PROVIDED ON SECOND FLOOR WINDOWS WHERE THE TOP |
| | OF THE WINDOW SILL OF AN OPERABLE WINDOW IS LOCATED |
| | LESS THAN 24" ABOVE THE FINISHED FLOOR . SEC. R312.2 |
| | FBC RESIDENTIAL. |
| | NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND |
| | FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL |
| | PROTECTION IF REQUIRED. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | UNABLE TO VERIFY IF WINDOW FALL PROTECTION IS REQUIRED |
| | |
| | ORIGINAL COMMENT: |
| | 5- PLANS DON'T PROVIDE ANY INFORMATION FOR THE NEW |
| | SPIRAL STAIR. |
| | UNABLE TO CHECK EGRESS. SEC. R311.7.10.1 |
| | FBC-RESIDENTIAL. SPECIFY STAIR SIZE AND TREAD AND |
| | RISERS DIMENSIONS. PROVIDE COMPLETE |
| | DETAILS/SPECIFICATIONS FOR CONSTRUCTION: FOOTING, |
| | ANCHORING, ETC. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | PLANS DON'T SPECIFY SIZE OF SPIRAL STAIR. UNABLE TO |
| | VERIFY EGRESS. |
| | ALSO, DETAIL 1 ON SHEET A3.20 DOESN'T SPECIFY THE |
| | HEIGHT OF THE HANDRAIL AND IT LOOKS LIKE THE STAIR |
| | HANDRAIL PICKETS SPACING DON'T COMPLY WITH THE OPENING |
| | LIMITATIONS OF SEC. R312.1.3 FBC-RESIDENTIAL. |
| | |
| | 6- OK. |
| | 7- OK. |
| | 8- OK. |
| | |
| | ORIGINAL COMMENT: |
| | 9- PLANS DON'T PROVIDE ANY DETAILS/SPECIFICATIONS FOR |
| | THE CONSTRUCTION AND INSTALLATION OF NEW CANVAS AWNINGS |
| | AS SHOWN ON THE EAST ELEVATION. PROVIDE COMPLETE |
| | DETAILS/SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | TYPICAL AWING DETAIL ON SHEET A3.20 DOESN'T PROVIDE |
| | FASTENING SPECIFICATIONS. DESIGNER OF RECORD TO PROVIDE |
| | THE INFORMATION TO SHOW COMPLIANCE WITH WIND DESIGN. |
| | SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | 10- OK. |
| | 11- OK. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| | REVISION MADE WILL HELP TO EXPEDITE THE AUDIT PROCESS. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |