| Date |
Text |
| 2022-06-21 16:55:29 | RESIDENTIAL (R3) ALTERATION FOURTH BUILDING AUDIT. |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21110016 (MAIN HOUSE) |
| | |
| | NOTE: |
| | THIS IS A LEVEL 2 ALTERATION. SEC. 603 FBC-EXISTING |
| | BUILDING. SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 1-OK. |
| | 2-OK. |
| | |
| | 3- NEW STAIRWAYS: |
| | A)PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE |
| | CONSTRUCTION OF THE NEW STAIRWAYS SHOWING COMPLIANCE |
| | WITH SEC. R11.7 FBC-RESIDENTIAL. |
| | |
| | PREVIOUS COMMENT: |
| | (1)EAST SIDE STAIRS: CLARIFY TREAD DIMENSIONS. FLOOR |
| | PLAN SHOWS 48'-0" AND 96'-0" TREADS?. |
| | (NOTE: SEE SHEET A1.10. ALSO, TO AVOID MORE CONFLICTS |
| | AND UNNECESSARY DELAYS KEEP IN MIND THAT STAIRWAY |
| | LANDING CAN NOT BE LESS THAN 36" AND READ SEC. R311.7.5 |
| | FOR RISER AND TREAD REQUIREMENTS). |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. REVISED PLAN SHOWS 2'-0" STAIR BOTTOM |
| | LANDING. THE MINIMUM BOTTOM LANDING DIMENSION OF 36" |
| | WAS NOT PROVIDED AS REQUESTED ON PREVIOUS COMMENT TO |
| | AVOID MORE DELAYS. REVISE AS REQUIRED. SEC. R11.7.6 |
| | FBC-RESIDENTIAL. |
| | |
| | 4- OK. |
| | 5- OK. |
| | 6- OK. |
| | |
| | 7- PLANS DON'T PROVIDE ANY DETAILS/SPECIFICATIONS FOR |
| | THE CONSTRUCTION AND INSTALLATION OF NEW CANVAS AWNINGS |
| | AS SHOWN ON THE EAST ELEVATION. PROVIDE COMPLETE |
| | DETAILS/SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | PREVIOUS COMMENT: |
| | TYPICAL AWNING DETAIL ON SHEET A3.20 DOESN'T PROVIDE |
| | FASTENING SPECIFICATIONS. DESIGNER OF RECORD TO PROVIDE |
| | THE INFORMATION TO SHOW COMPLIANCE WITH WIND DESIGN. |
| | SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. PROVIDE COMPLETE INFORMATION FOR AWNING |
| | INSTALLATION OR PROVIDE COMPLETE INFORMATION UNDER A |
| | SEPARATE PERMIT. |
| | |
| | 8- OK. |
| | 9- OK. |
| | 10- OK. |
| | 11- OK. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| | REVISION MADE WILL HELP TO EXPEDITE THE AUDIT PROCESS. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |