| 2021-12-17 10:58:03 | RESIDENTIAL (R3) ALTERATION BUILDING AUDIT. |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21110016 |
| | |
| | NOTE: |
| | THIS IS A LEVEL 2 ALTERATION. SEC. 603 FBC-EXISTING |
| | BUILDING. SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 1-PLANS DON'T SPECIFY CURRENT CODE AND THE DESIGN |
| | CRITERIA. SEC. 107.3.5.3 CITY AMENDMENTS. |
| | ARCHITECT TO PROVIDE ALL THE WIND DESIGN CRITERIA AS |
| | REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. SPECIFY THE |
| | ULTIMATE AND NOMINAL WIND LOAD, BUILDING EXPOSURE, |
| | BUILDING MEAN ROOF HEIGHT. ALSO, SPECIFY THE COMPONENTS |
| | AND CLADDING DESIGN PRESSURES FOR DOORS AND WINDOWS. |
| | |
| | 2- PLANS DON'T PROVIDE ANY STRUCTURAL |
| | DETAILS/SPECIFICATIONS. ARCHITECT NEEDS TO PROVIDE |
| | COMPLETE INFORMATION AS REQUIRED BY SEC. SEC. 107.3.5.3 |
| | CITY AMENDMENTS AND SEC. R301.1 FBC-RESIDENTIAL: |
| | |
| | A) PROVIDE COMPLETE OPENING FRAMING |
| | DETAILS/SPECIFICATIONS FOR NEW WINDOWS AND DOORS. |
| | SPECIFY ALL FRAMING MEMBERS SIZES AND CONNECTORS AT |
| | EACH END. |
| | |
| | 3- NEW STAIRWAYS: |
| | A)PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE |
| | CONSTRUCTION OF THE NEW STAIRWAYS SHOWING COMPLIANCE |
| | WITH SEC. R11.7 FBC-RESIDENTIAL. |
| | |
| | B)A LANDING COMPLYING WITH SEC. R311.3 FBC-RESIDENTIAL |
| | IS REQUIRED IN THE STAIRWAY BY THE NEW DOUBLE FRENCH |
| | DOORS. |
| | |
| | C) HANDRAIL IS REQUIRED ON THE NEW STAIRWAY BY THE NEW |
| | DOUBLE FRENCH DOORS. |
| | SEC. R311.7.8 FBC-RESIDENTIAL |
| | |
| | 4-PLANS DON'T PROVIDE ANY DETAILS/SPECIFICATIONS FOR |
| | THE GUARDRAIL AND HANDRAIL. |
| | PROVIDE COMPLETE DETAILS/SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH TABLE R301.5, SEC. R312.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 5- WINDOW ADJACENT TO THE SINGLE FRENCH DOOR NEEDS TO |
| | HAVE SAFETY GLAZING AS REQUIRED BY SEC. R308.4.2 |
| | FBC-RESIDENTIAL. SHOW COMPLIANCE. |
| | |
| | 6- PROVIDE COMPLETE WALL SECTION SPECIFYING WALL |
| | SHEATHING THICKNESS AND FASTENING, AND ALL EXTERIOR AND |
| | INTERIOR FINISHES. SEC. 107..3.5.3 CITY AMENDMENTS. |
| | ALSO, PROVIDE SPECIFICATIONS FOR THE REQUIRED TWO WATER |
| | RESISTIVE BARRIERS WHEN STUCCO IS APPLIED TO WOOD AS |
| | REQUIRED BY SEC. R703.7.3 FBC-RESIDENTIAL. |
| | |
| | 7- PLANS DON'T PROVIDE ANY DETAILS/SPECIFICATIONS FOR |
| | THE CONSTRUCTION AND INSTALLATION OF NEW CANVAS AWNINGS |
| | AS SHOWN ON PLANS. PROVIDE COMPLETE |
| | DETAILS/SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR: |
| | A)OUTSWING ENTRY DOOR AS SHOWN ON PLANS. |
| | |
| | B) INSWING FRENCH DOORS AS SHOWN ON PLANS. |
| | |
| | 9- DESIGNER OF RECORD TO REVIEW/APPROVE ABOVE PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | |
| | 10- MULLION: NEITHER PLANS OR PRODUCT APPROVAL |
| | SUBMITTED SPECIFY SIZE OF MULLION TO BE USED BETWEEN |
| | THE FRENCH DOOR AND THE WINDOW AS SHOWN ON PLANS. |
| | SPECIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | 11- POOL AND POOL PAVERS ARE TO BE DONE UNDER SEPARATE |
| | PERMITS. SEC. 105.1 CITY AMENDMENTS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |