| 2022-02-16 13:02:18 | ELECTRIC REVIEW FAILED |
| | |
| | 1) COMMENTS CONCERNING SUPPLY CONDUCTORS REQUIRED TO |
| | HAVE GROUND FAULT PROTECTION HAVE NOT BEEN ADDRESSED AS |
| | PER DRAWING SUBMITTED (SUPPLY, KEY WORD) |
| | 555.3 GROUND-FAULT PROTECTION. THE OVERCURRENT |
| | PROTECTIVE |
| | DEVICES THAT SUPPLY THE MARINA, BOATYARDS, AND |
| | COMMERCIAL AND |
| | NONCOMMERCIAL DOCKING FACILITIES SHALL HAVE |
| | GROUND-FAULT PROTECTION |
| | NOT EXCEEDING 30 MA. |
| | |
| | 2) COMMENT CONCERNING BRANCH CIRCUIT TAP CONDUCTORS |
| | HAVE NOT BEEN ADDRESSED PER DRAWINGS SUBMITTED. |
| | CONDUCTORS FEEDING RECEPTACLES MUST HAVE OVERCURRENT |
| | PROTECTION AS REQUIRED PER NEC 210.20. BRANCH-CIRCUIT |
| | CONDUCTORS |
| | AND EQUIPMENT SHALL BE PROTECTED BY OVERCURRENT |
| | PROTECTIVE |
| | DEVICES THAT HAVE A RATING OR SETTING THAT COMPLIES |
| | WITH 210.20(A) |
| | THROUGH (D). |
| | THE ONLY BRANCH CIRCUIT TAPS ALLOWED AS PER NEC IS |
| | STATED IN 210.19(A)(3) (HOUSEHOLD COOKING EQUIPMENT) |
| | EXCEPTIONS AND 210.19(A)(4) OTHER LOADS (EXCEPTIONS) |
| | |
| | 3) COMMENT CONCERNING RELEVANT INFORMATION HAS NOT BEEN |
| | ADDRESSED. PROVIDE A RISER DIAGRAM DETAILING ALL |
| | CONDUCTORS, OVERCURRENT PROTECTION AND LOAD |
| | CALCULATIONS OF THE PANEL OF ORIGIN AS PER NEC 215.5 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |