Plan Review Notes
Plan Review Notes For Permit 21101426
Permit Number 21101426
Review Stop B
Sequence Number 1
Notes
Date Text
2021-11-17 13:35:20PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENGINEER'S DRAWINGS SPECIFY THAT THIS PROJECT IS
 LOCATED IN EXPOSURE CATEGORY IS B. THIS PROJECT IS
 ACTUALLY LOCATED IN EXPOSURE CATEGORY C PER
 FBC-R301.2.1.4.
  
 2) ON 004 ELEVATION DETAIL SHEET 1 OF 1 THERE IS A
 CONFLICT IN THE RISK CATEGORY. IN THE UPPER LEFT HAND
 CORNER THE RISK CATEGORY IS SPECIFIED AS I AND IN THE
 LOWER RIGHT HAND IT IS SPECIFIED AS II. THE ULTIMATE
 WIND SPEED IS SPECIFIED AS 160 MPH WHICH IS CORRECT FOR
 RISK CATEGORY I, HOWEVER. IT WOULD BE 170 MPH FOR RISK
 CATEGORY II. SEE FBC-R301.2.1.1.1.1
  