| Date |
Text |
| 2022-02-25 12:27:37 | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT-21101420 |
| | 2/23/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| | 2020 |
| | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| | EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED PLUMBING COMMENTS |
| | FROM THE 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL |
| | NOTES IN CAPS |
| | |
| | 1) FAILED SHEETS ALS1.1 & ALS1.2: THE PLUMBING FIXTURE |
| | CALCULATIONS ARE INCORRECT. BASED ON TABLE 403.1 FBC P |
| | AND THE OCCUPANT LOADS SHOWN, FIXTURES REQUIRED ARE 8 |
| | MALE AND 8 FEMALE WATER CLOSETS, 7 MALE AND 7 FEMALE |
| | LAVATORIES, AND 6 DRINKING FOUNTAINS. CALCULATIONS |
| | SHALL BE BASED ON A MIXED OCCUPANCY USING PERCENTAGES. |
| | DRINKING FOUNTAIN CALCULATIONS USING PERCENTAGES: |
| | ASSEMBLY- .94 + BUSINESS- 0.196 + EDUCATIONAL- 399 = |
| | 5.126- 6 DRINKING FOUNTAINS REQUIRED. PLEASE REVISE THE |
| | CALCULATIONS AND INDICATE THE PROVIDED NUMBER OF |
| | PLUMBING FIXTURES. THE BUSINESS OCCUPANT SUB-TOTAL OF |
| | 43 IS INCORRECT. THE CORRECTED SUB-TOTAL IS 138. |
| | CONCERNING THE DRINKING FOUNTAINS, THE INCREASED LOAD |
| | RESULTS IN A FIXTURE CALCULATION OF 5.2 OR A TOTAL OF 6 |
| | DRINKING FOUNTAINS REQUIRED. PLEASE NOTE WATER |
| | DISPENSERS MAY BE SUBSTITUTED FOR NOT MORE THAN 50% OF |
| | THE REQUIRED DRINKING FOUNTAINS AND MUST COMPLY WITH |
| | SEC. 410.1 FBC P- WATER DISPENSERS SHALL CONFORM TO NSF |
| | 61, SECTION 9. ELECTRICALLY OPERATED, REFRIGERATED |
| | DRINKING WATER COOLERS AND WATER DISPENSERS SHALL BE |
| | LISTED AND LABELED IN ACCORDANCE WITH UL 399. REACH |
| | RANGES AND OPERABLE PARTS OF THE DISPENSERS SHALL BE IN |
| | COMPLIANCE WITH SECS. 308 & 309 FBC ACC. |
| | |
| | 2) FAILED. ALS1.1 & ALS1.2: LABELS THE RESTROOMS ON THE |
| | PLANS AS EITHER MALE, FEMALE, OR UNISEX- SEC. 403.2 FBC |
| | P. SECTION 403.2 STATES WHERE PLUMBING FIXTURES ARE |
| | REQUIRED, SEPARATE FACILITIES FOR EACH SEX SHALL BE |
| | PROVIDED. PLEASE LABEL THE FACILITES AS EITHER MALE OR |
| | FEMALE. |
| | |
| | 3) FAILED. ARCH. & PLUMB. PLANS: SHOW THE LOCATIONS OF |
| | THE MISSING REQUIRED DRINKING FOUNTAINS AND PROVIDE |
| | PLUMBING PIPING DETAILS- SEC. 107.2.1 WPB. THE CURRENT |
| | PLANS SHOW ONLY ONE HI/LO. REFER TO SECS. 211 AND 602 |
| | FBC ACC FOR ACCESSIBILITY REQUIREMENTS. SEE COMMENT #1 |
| | ABOVE. |
| | |
| | 12) FAILED. A1.1.1: THE PLAN SHOWS A CATERING KITCHEN |
| | WITH A 3-COMPARTMENT SINK WHICH IS TYPICALLY USED FOR |
| | POT WASHING OR FOOD PREP. THE DRAINAGE FROM THE SINK |
| | SHALL DISCHARGE INTO A GREASE WASTE LINE CONNECTED TO A |
| | GREASE INTERCEPTOR- SEC. 1003.3.1 FBC P. GREASE WASTE |
| | DRAIN AND VENT ISOMETRIC DRAWING AND A WATER RISER FOR |
| | THE KITCHEN FIXTURES WERE NOT PROVIDED SEC. 107.3.5.1.3 |
| | WPB. PLEASE NOTE THE HAND SINK SHALL NOT DRAIN INTO THE |
| | GREASE INTERCEPTOR- SEC. 1003.3.1 FBC P. |
| | |
| | 15) P101A & P201: A LINT INTERCEPTOR IS REQUIRED FOR |
| | THE CLOTHES WASHING MACHINE FBC P SEC. 1003.6 FBC P. |
| | SHOW THE LOCATION OF THE INTERCEPTOR, PROVIDE AN |
| | EQUIPMENT SCHEDULE, AND PROVIDE PIPING DETAILS. THE |
| | LINT INTERCEPTOR DETAIL ON P501 IS A COPY AND PASTE |
| | DETAIL FOR A SINK AND NOT THE FACILITY WASHING MACHINE. |
| | |
| | 17) FAILED. P110: PROVIDE OVERFLOW DRAINAGE ROOF |
| | DRAINAGE CALCULATIONS AND SHOW THE LOCATIONS AND SIZES |
| | OF THE OVERFLOW DRAINS AND DRAINAGE LOCATIONS- |
| | SECS-1108.1, 1108.2, 1108.3 FBC P. PLEASE SHOW THE |
| | LOCATIONS OF THE EXISTING OVERFLOW SCUPPERS OR OVERFLOW |
| | DRAINS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |