Plan Review Notes
Plan Review Notes For Permit 21101420
Permit Number 21101420
Review Stop G
Sequence Number 3
Notes
Date Text
2022-02-25 12:28:443RD REVIEW FBC-2020 GAS
 PERMIT-21101420
 2/23//22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P101B & P203: THE 1-INCH SCHEDULE 40 METALLIC
 IS UNDERSIZED FOR A LOAD OF 1,779 CFH AT 2540 FT.
 DEVELOPED LENGTH, AND ALSO FOR THE INDIVIDUAL LOAD OF
 1280 CFH FOR THE GENERATOR- TABLE 402.4(5) FBC FG. THE
 MINIMUM SIZE REQUIRED IS 1-1/4-INCH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  