Plan Review Notes
Plan Review Notes For Permit 21101420
Permit Number 21101420
Review Stop P
Sequence Number 2
Notes
Date Text
2022-01-27 16:27:362ND REVIEW FBC-2020 PLUMBING
 PERMIT-21101420
 1/27/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS ALS1.1 & ALS1.2: THE PLUMBING FIXTURE
 CALCULATIONS ARE INCORRECT. BASED ON TABLE 403.1 FBC P
 AND THE OCCUPANT LOADS SHOWN, FIXTURES REQUIRED ARE 8
 MALE AND 8 FEMALE WATER CLOSETS, 7 MALE AND 7 FEMALE
 LAVATORIES, AND 6 DRINKING FOUNTAINS. CALCULATIONS
 SHALL BE BASED ON A MIXED OCCUPANCY USING PERCENTAGES.
 DRINKING FOUNTAIN CALCULATIONS USING PERCENTAGES:
 ASSEMBLY- .94 + BUSINESS- 0.196 + EDUCATIONAL- 399 =
 5.126- 6 DRINKING FOUNTAINS REQUIRED. PLEASE REVISE THE
 CALCULATIONS AND INDICATE THE PROVIDED NUMBER OF
 PLUMBING FIXTURES.
  
 2) ALS1.1 & ALS1.2: LABELS THE RESTROOMS ON THE PLANS
 AS EITHER MALE, FEMALE, OR UNISEX- SEC. 403.2 FBC P.
  
 3) ARCH. & PLUMB. PLANS: SHOW THE LOCATIONS OF THE
 MISSING REQUIRED DRINKING FOUNTAINS AND PROVIDE
 PLUMBING PIPING DETAILS- SEC. 107.2.1 WPB. THE CURRENT
 PLANS SHOW ONLY ONE HI/LO. REFER TO SECS. 211 AND 602
 FBC ACC FOR ACCESSIBILITY REQUIREMENTS.
  
 4) SHEET A1.2.1: PROVIDE ENLARGED DRAWINGS FOR STUDENT
 RESTROOMS 216A, 217A, & 218A SHOWING ACCESSIBLE
 PLUMBING FIXTURE DETAILS AND DIMENSIONS IN COMPLIANCE
 WITH SEC. 604.9 FBC ACC.
  
 5) A9.0.1, A9.0.2: SHOW THE KNEE AND TOE CLEARANCES FOR
 THE ACCESSIBLE LAVATORIES- SEC. 606.2 & FIGURES 306.2 &
 306.3 FBC ACC.
  
 6) A9.0.1, A9.0.2: SHOW THE HEIGHTS OF THE MIRRORS FROM
 THE FINISHED FLOORS TO THE REFLECTIVE SURFACES- SEC.
 603.3 FBC ACC.
  
 7) A9.0.1, A9.0.2: SHOW THE MINIMUM 42-INCH LENGTH
 MEASUREMENT OF THE WATER CLOSET SIDE WALL GRAB BAR, AND
 THE MINIMUM 54-INCH MINIMUM EXTENSION FOR THE REAR
 WALL- FIGURE 604.5.1 FBC ACC.
  
  
 8) A9.0.1, A9.0.2: SHOW THE MINIMUM 36-IINCH LENGTH
 MEASUREMENT OF THE WATER CLOSET GRAB BAR, AND THE
 24-INCH EXTENSION FROM THE CENTERLINE OF THE WATER
 CLOSET TO THE OPEN SIDE- FIGURE 604.5.2 FBC ACC.
  
 9) A9.0.2: SHOW THE HEIGHTS OF THE SHOWER GRAB BARS
 MEASURED FROM THE FINISHED FLOOR TO THE TOPS OF THE
 GRIPPING SURFACES- SECS 608.3.2 AND 609.4 FBC ACC.
  
 10) A9.05: SHOW THE HEIGHTS OF THE WATER CLOSET AND
 SHOWER GRAB BARS MEASURED TO THE TOPS OF THE GRIPPING
 SURFACES- SEC. 609.4 FBC ACC.
  
 11) A9.05: THE SHOWER CONTROLS SHALL BE LOCATED ON THE
 SIDE WALL FARTHEST FROM DOOR OPENING IN COMPLIANCE WITH
 SEC. 608.5.3 FBC ACC.
  
 12) A1.1.1: THE PLAN SHOWS A CATERING KITCHEN WITH A
 3-COMPARTMENT SINK WHICH IS TYPICALLY USED FOR POT
 WASHING OR FOOD PREP. THE DRAINAGE FROM THE SINK SHALL
 DISCHARGE INTO A GREASE WASTE LINE CONNECTED TO A
 GREASE INTERCEPTOR- SEC. 1003.3.1 FBC P- A GREASE
 INTERCEPTOR SHALL BE REQUIRED TO RECEIVE THE DRAINAGE
 FROM FIXTURES AND EQUIPMENT WITH GREASE-LADEN WASTE
 LOCATED IN FOOD PREPARATION AREAS, SUCH AS IN
 RESTAURANTS, HOTEL KITCHENS, HOSPITALS, SCHOOL
 KITCHENS, BARS, FACTORY CAFETERIAS AND CLUBS. FIXTURES
 AND EQUIPMENT SHALL INCLUDE POT SINKS, PRERINSE SINKS;
 SOUP KETTLES OR SIMILAR DEVICES; WOK STATIONS; FLOOR
 DRAINS, OR SINKS INTO WHICH KETTLES ARE DRAINED;
 AUTOMATIC HOOD WASH UNITS AND DISHWASHERS WITHOUT
 PRERINSE SINKS. PLEASE NOTE A SEPARATE PERMIT IS
 REQUIRED FOR INSTALLATION OF THE INTERCEPTOR- SECTION
 105.1 & 107.2.1 WPB. A) NOTE 18 INDICATES NEW KITCHEN
 EQUIPMENT WHICH IS NOT SHOWN ON THE PLAN. PLEASE
 PROVIDE A COMPLETE EQUIPMENT PLAN AND EQUIPMENT
 SCHEDULE. REVISE THE PLUMBING PLANS TO SHOW LOCATIONS
 OF ALL PLUMBING FIXTURES AND PLUMBING PIPING- SEC.
 107.2.1 WPB. B) PROVIDE AN INDIRECT WASTE DETAIL FOR
 THE 3-COMPARTMENT SINK- SEC. 802.1.1 FBC P.
  
 12) P101A & P201: PROVIDE VENTING FOR THE MS-1 AND FD-1
 IN JAN.107. THE WASHING MACHINE AND SV-1 CANNOT BE PART
 OF A COMBINATION WASTE AND VENT SYSTEM- SECS. 911, 912,
 & 915 FBC P.
  
 13) P101A & P201: NON-COMPLIANT WET VENTS SHOWN IN
 ROOMS 121A, 123A, & 215A. REFER TO SEC. 912.2.1 FBC P-
 NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN SHALL
 DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN
 CONNECTION.
  
 14) P101A & P201: PLEASE SHOW A 3-INCH VERTICAL STACK
 FOR THE WASHING MACHINE- SEC. 406.2 FBC P.
  
 15) P101A & P201: A LINT INTERCEPTOR IS REQUIRED FOR
 THE CLOTHES WASHING MACHINE FBC P SEC. 1003.6 FBC P.
 SHOW THE LOCATION OF THE INTERCEPTOR, PROVIDE AN
 EQUIPMENT SCHEDULE, AND PROVIDE PIPING DETAILS.
  
 16) P110: PROVIDE THE RAIN FALL RATE USED FOR THE
 CALCULATIONS AND CONDUCTOR SIZING- SEC. 1106.1 FBC P.
  
 17) P110: PROVIDE OVERFLOW DRAINAGE ROOF DRAINAGE
 CALCULATIONS AND SHOW THE LOCATIONS AND SIZES OF THE
 OVERFLOW DRAINS AND DRAINAGE LOCATIONS- SECS-1108.1,
 1108.2, 1108.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  