Plan Review Notes
Plan Review Notes For Permit 21101420
Permit Number 21101420
Review Stop G
Sequence Number 2
Notes
Date Text
2022-01-28 09:39:392ND REVIEW FBC-2020 GAS
 PERMIT-21101420
 1/27/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P101B & P203: SHOW THE GAS METER LOCATION-
 SEC. 402.1 FBC FG.
  
 2) P203 GAS RISER: SHOW THE CFH LOAD OF THE GENERATOR-
 SEC. 402.2 FBC FG.
  
 3) P203 GAS RISER: SHOW THE BRANCH PIPING LENGTHS- SEC.
 402.4.1 FBC FG.
  
 4) P203 GAS RISER: PROVIDE THE PIPE SIZING TABLE FOR
 THE TRAC PIPE- SECS .402.4 & 403.5.5 FBC FG.
  
 5) P203 GAS RISER: IDENTIFY THE TYPE OF ABOVEGROUND
 PIPING TO BE INSTALLED. IT APPEARS TO BE SCHEDULE 40
 METALLIC- SEC. 403.4 FBC FG.
  
 6) P101B & P203: PROVIDE CONTROL OPERATION DETAILS FOR
 THE SOLENOID VALVE GSV-1. WHAT SYSTEM WILL TRIGGER THE
 VALVE TO CLOSE? SHOW THE ELECTRICAL CIRCUITRY AND
 CONNECTIONS FOR THE VALVE- SEC. 409.1.1 FBC FG. PLEASE
 SHOW THE LOCATION OF GSV-2 AND PROVIDE CONTROL
 OPERATION DETAILS.
  
 7) P101B: REFER TO THE SUBMITTED MANUFACTURER'S
 SPECIFICATIONS FOR THE GAS WATER HEATER AND SHOW THE
 TOTAL RUN LENGTHS OF THE GAS WATER HEATER INTAKE AND
 EXHAUST DUCTS AND THE TYPE OF DUCT MATERIAL- SECS.
 503.2.3 & 503.6.10.3 FBC FG. PLEASE CLARIFY IF THE UNIT
 IS DIRECT OR POWER VENT- DV OR PV. A COMPLETE REVIEW OF
 THE WATER HEATER CANNOT BE COMPLETELY WITHOUT THE
 INSTALLATION MANUAL. PLEASE SUBMIT THE MANUAL- SEC.
 503.2.3 FBC FG.
  
 8) P101B: SHOW THE WATER HEATER INTAKE AND EXHAUST DUCT
 TERMINATION CLEARANCES FROM GRADE, AND FROM AIR INTAKES
 AND OPERABLE OPENINGS INTO THE BUILDING- SEC. 503.8 FBC
 FG.
  
 9) P101B & P203: PROVIDE A CONDENSATE DISPOSAL DIAGRAM
 FOR THE CONDENSING WATER HEATER IN COMPLIANCE WITH SEC.
 307.2 & 307.3 FBC FG. SHOW THE TYPE AND SIZE OF PIPING,
 THE PIPING RUN AND TERMINATION LOCATION. PLEASE NOTE
 THAT A NEUTRALIZING DEVICE IS REQUIRED PER SEC. 803.1
 FBC P BECAUSE OF THE CORROSIVE CONTENT OF THE
 CONDENSATE LIQUID. THE CONDENSATE FROM THE DEVICE SHALL
 DISCHARGE OUTSIDE OF THE BUILDING INTO A DRYWELL OR
 GROUND A MINIMUM OF 12-INCHES AWAY FROM THE BUILDING.
  
 10) P101B & P203: THE WATER HEATER SPECS INDICATE A
 RELIEF VALVE WHICH WILL REQUIRE A RELIEF VALVE
 DISCHARGE PIPE. PLEASE PROVIDE A DIAGRAM SHOWING THE
 TYPE AND SIZE OF RELIEF PIPE, PIPE RUN AND DISCHARGE
 LOCATION- SEC. 624.1.1 FBC FG & 504.6 FBC P.
  
 11) P101B & P203: PLEASE PLACE A NOTE TO INDICATE THE
 GENERATOR SHALL BE INSTALLED UNDER A SEPARATE PERMIT-
 SECS. 105.1 & 107.2.1 WPB. A COMPLETE REVIEW OF THE
 GENERATOR INSTALLATION IS NOT BEING PERFORMED AT THIS
 TIME. A) PLEASE PROVIDE THE CLEARANCE DISTANCES ON
 P101B THAT ARE SHOWN ON SP-1.
  
 12) THE SUBMITTED ENERGYGAUGE COMPLIANCE SUBMITTAL DOES
 NOT PROVIDE COMPLIANCE DATA FOR THE WATER HEATER AND
 WATER PIPING- SEC. C101.5 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  