| 2022-01-28 09:39:39 | 2ND REVIEW FBC-2020 GAS |
| | PERMIT-21101420 |
| | 1/27/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| | EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P101B & P203: SHOW THE GAS METER LOCATION- |
| | SEC. 402.1 FBC FG. |
| | |
| | 2) P203 GAS RISER: SHOW THE CFH LOAD OF THE GENERATOR- |
| | SEC. 402.2 FBC FG. |
| | |
| | 3) P203 GAS RISER: SHOW THE BRANCH PIPING LENGTHS- SEC. |
| | 402.4.1 FBC FG. |
| | |
| | 4) P203 GAS RISER: PROVIDE THE PIPE SIZING TABLE FOR |
| | THE TRAC PIPE- SECS .402.4 & 403.5.5 FBC FG. |
| | |
| | 5) P203 GAS RISER: IDENTIFY THE TYPE OF ABOVEGROUND |
| | PIPING TO BE INSTALLED. IT APPEARS TO BE SCHEDULE 40 |
| | METALLIC- SEC. 403.4 FBC FG. |
| | |
| | 6) P101B & P203: PROVIDE CONTROL OPERATION DETAILS FOR |
| | THE SOLENOID VALVE GSV-1. WHAT SYSTEM WILL TRIGGER THE |
| | VALVE TO CLOSE? SHOW THE ELECTRICAL CIRCUITRY AND |
| | CONNECTIONS FOR THE VALVE- SEC. 409.1.1 FBC FG. PLEASE |
| | SHOW THE LOCATION OF GSV-2 AND PROVIDE CONTROL |
| | OPERATION DETAILS. |
| | |
| | 7) P101B: REFER TO THE SUBMITTED MANUFACTURER'S |
| | SPECIFICATIONS FOR THE GAS WATER HEATER AND SHOW THE |
| | TOTAL RUN LENGTHS OF THE GAS WATER HEATER INTAKE AND |
| | EXHAUST DUCTS AND THE TYPE OF DUCT MATERIAL- SECS. |
| | 503.2.3 & 503.6.10.3 FBC FG. PLEASE CLARIFY IF THE UNIT |
| | IS DIRECT OR POWER VENT- DV OR PV. A COMPLETE REVIEW OF |
| | THE WATER HEATER CANNOT BE COMPLETELY WITHOUT THE |
| | INSTALLATION MANUAL. PLEASE SUBMIT THE MANUAL- SEC. |
| | 503.2.3 FBC FG. |
| | |
| | 8) P101B: SHOW THE WATER HEATER INTAKE AND EXHAUST DUCT |
| | TERMINATION CLEARANCES FROM GRADE, AND FROM AIR INTAKES |
| | AND OPERABLE OPENINGS INTO THE BUILDING- SEC. 503.8 FBC |
| | FG. |
| | |
| | 9) P101B & P203: PROVIDE A CONDENSATE DISPOSAL DIAGRAM |
| | FOR THE CONDENSING WATER HEATER IN COMPLIANCE WITH SEC. |
| | 307.2 & 307.3 FBC FG. SHOW THE TYPE AND SIZE OF PIPING, |
| | THE PIPING RUN AND TERMINATION LOCATION. PLEASE NOTE |
| | THAT A NEUTRALIZING DEVICE IS REQUIRED PER SEC. 803.1 |
| | FBC P BECAUSE OF THE CORROSIVE CONTENT OF THE |
| | CONDENSATE LIQUID. THE CONDENSATE FROM THE DEVICE SHALL |
| | DISCHARGE OUTSIDE OF THE BUILDING INTO A DRYWELL OR |
| | GROUND A MINIMUM OF 12-INCHES AWAY FROM THE BUILDING. |
| | |
| | 10) P101B & P203: THE WATER HEATER SPECS INDICATE A |
| | RELIEF VALVE WHICH WILL REQUIRE A RELIEF VALVE |
| | DISCHARGE PIPE. PLEASE PROVIDE A DIAGRAM SHOWING THE |
| | TYPE AND SIZE OF RELIEF PIPE, PIPE RUN AND DISCHARGE |
| | LOCATION- SEC. 624.1.1 FBC FG & 504.6 FBC P. |
| | |
| | 11) P101B & P203: PLEASE PLACE A NOTE TO INDICATE THE |
| | GENERATOR SHALL BE INSTALLED UNDER A SEPARATE PERMIT- |
| | SECS. 105.1 & 107.2.1 WPB. A COMPLETE REVIEW OF THE |
| | GENERATOR INSTALLATION IS NOT BEING PERFORMED AT THIS |
| | TIME. A) PLEASE PROVIDE THE CLEARANCE DISTANCES ON |
| | P101B THAT ARE SHOWN ON SP-1. |
| | |
| | 12) THE SUBMITTED ENERGYGAUGE COMPLIANCE SUBMITTAL DOES |
| | NOT PROVIDE COMPLIANCE DATA FOR THE WATER HEATER AND |
| | WATER PIPING- SEC. C101.5 FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |