| 2022-01-25 14:36:30 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT:21101420 |
| | ADD: 2400 METROCENTRE BLVD. EAST |
| | CONT: QUEST CONTRACTING, LLC |
| | TEL: 561-691-9400 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. JAN. 25TH/ 2022 |
| | ACTION: DENIED |
| | |
| | 1-3) COMPLIED. |
| | |
| | |
| | 4) BUILDING PROVISO: SHEETS S1.1.2 & S4.0.1 AND OTHER |
| | SHEETS SHOW EITHER FIELD WELDING OR BOLTED CONNECTIONS. |
| | WELDED OR BOLTED CONNECTIONS. THIS BUILDING CONTAINS |
| | EITHER BOLTED AND OR WELDED CONNECTIONS. THE CONTRACTOR |
| | IS REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE |
| | WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED. |
| | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666 OR ACTING CHIEF BUILDING INSPECTOR |
| | RICHARD BRUNELLE AT 561-805-6670. |
| | |
| | 5) SUBMITTED PRODUCT APPROVALS FOR ROOF TILE SYSTEMS: |
| | FL 2533-R26 CERTAINTEED MODIFIED ROOFING SYSTEMS P. |
| | 72OF 75 SUB-SYSTEM R-25 -105MPH VASD |
| | FL 7473-R9 EAGLE ROOFING PRODUCTS, FLAT ROOF TILE P. 6 |
| | OF 7 6.3.3 ADHESIVE SET. |
| | ICP ADHESIVE POLYSET AH-160 FL 6332 |
| | FL 6332-R9 ICP ADHESIVE & SEALANTS. P 5 OF 12 TABLE 1 |
| | FIELD TILES IN POLYSET AH-160 |
| | P 6 OF 12 HIP & RIDGE TILE IN POLYSET AH-160 DETAIL 5 |
| | EAST COAST METALS |
| | FL 9777-R15 OWENS CORNING UNDERLAYMENT 9777.7 PAGE 5 OF |
| | 7 STATES WEATHERLOCK SPECIALTY TILE & METAL (GREEN |
| | FACER) IS PERMITTED TO BE USED WITH ADHERED CLAY OR |
| | CONCRETE TILE ROOFING USING DUPONT TILE BOND ROOF TILE |
| | ADHESIVE. |
| | |
| | 5A) 2ND REQUEST. THE ISSUE WITH THE LISTED ROOFING |
| | PRODUCT APPROVAL IS WITH FL 9777-R15 OWENS CORNING |
| | UNDERLAYMENT 9777.7 PAGE 5 OF 7 STATES WEATHERLOCK |
| | SPECIALTY TILE & METAL (GREEN FACER) IS PERMITTED TO BE |
| | USED WITH ADHERED CLAY OR CONCRETE TILE ROOFING USING |
| | DUPONT TILE BOND ROOF TILE ADHESIVE. THE ROOFING |
| | ADHESIVE DUPONT TILE BOND IS NOT THE POLY SET AH-160 |
| | LISTED IN THE FL FL 6332-R9 ICP ADHESIVE & SEALANTS. P |
| | 5 OF 12, NO PRODUCT APPROVAL WAS SUBMITTED FOR THE |
| | DUPONT TILE BOND. |
| | |
| | 5B) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| | ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) ARE YOU ASKING FOR DEFERRED SUBMITTALS. 107.3.4.2 |
| | DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, |
| | DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF |
| | THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 1ST REVIEW COMMENTS. IDENTIFY GLAZING/ MULLIONS. PLEASE |
| | IDENTIFY IN THE PRODUCT APPROVAL BEFORE SUBMITTING TO |
| | DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, SILL |
| | HEIGTH, TYPE OF GLAZING, MULLION SIZE, LENGTH IF |
| | UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING |
| | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| | THE TESTS. |
| | |
| | 8-9 COMPLIED. |
| | |
| | 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |