| 2021-12-05 15:56:23 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21101420 |
| | 12/5/2021 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| | EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1. INDICATE ON THE PLAN THE REQUIRED CLEAR FLOOR SPACE |
| | FOR THE HANDICAPPED ACCESSIBLE URINAL SHALL COMPLY WITH |
| | FBC ACC SEC. 305. |
| | |
| | 2. MIRRORS SHALL BE MEASURED 40? TO THE REFLECTING |
| | SURFACE FROM THE FINISHED FLOOR PER FBC ACC SEC 603.3 |
| | |
| | 3. GRAB BARS SHALL BE 33-36? MEASURED FROM THE FINISHED |
| | FLOOR TO THE GRIPPING SURFACE. THE PLAN PAGE SHOWS IT |
| | BEING MEASURED TO THE CENTER OF THE GRAB BAR. PLEASE |
| | REVISE THIS DISCREPANCY. PLAN PAGE A 9.0.1 |
| | |
| | 4. MINIMUM 27? REQUIRED KNEE CLEAR FLOOR SPACE REQUIRED |
| | UNDER LAVATORIES FBC ACC SEC 306.3 |
| | |
| | 5. THE ACCESSIBLE URINAL SHALL HAVE A MINIMUM OPENING |
| | OF 36? MEASURED FROM THE CENTER OF THE URINAL TO EACH |
| | SIDE WALL PER FBC ACC SEC 305. |
| | |
| | 6. PLEASE INDICATE THE AGES OF THE CHILDREN GOING TO BE |
| | USING THE RESTROOMS ON PLAN PAGES 125A, 217A, 126, 218 |
| | |
| | 7. PROVIDE DETAILS ON PLUMBING ABBREVIATIONS ON PLAN |
| | PAGE P101B |
| | |
| | 8. LINT INTERCEPTOR IS REQUIRED FOR THE CLOTHES WASHING |
| | MACHINE FBC P SEC. 1003.6 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |