| 2021-11-24 13:12:03 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21101420 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M101: PLEASE ADD A NOTE ON THE DRAWING STATING |
| | THAT THE KITCHEN HOOD WILL REQUIRE A SEPARATE PERMIT |
| | APPLICATION AND SUBMITTAL FOR REVIEW AS IT WILL NOT BE |
| | REVIEWED UNDER THIS PERMIT. IF NO HOOD IS TO BE USED |
| | PLEASE EXPLAIN THE USE OF THE CATERING KITCHEN. |
| | |
| | 2) SHEET M101: PLEASE SHOW THE SUPPLY CFM?S AT THE |
| | GRILLES FOR AHU-1.3. FBC 107.2.1 |
| | |
| | 3) SHEET M101: PLEASE ADD A NOTE ON THE DRAWING STATING |
| | THAT THE REFRIGERATION EQUIPMENT WILL REQUIRE A |
| | SEPARATE PERMIT APPLICATION AND SUBMITTAL FOR REVIEW AS |
| | IT WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| | |
| | 4) PLEASE PROVIDE THE GLOBAL PLASMA SOLUTIONS |
| | CALCULATIONS. FBC M 403.2 |
| | |
| | 5) PLEASE SHOW THE CONDENSATE DRAIN PIPING MATERIAL, |
| | SIZE AND TERMINATION LOCATION. FBC M307 |
| | |
| | 6) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH |
| | USE OF SPACE. FBC M 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |