Plan Review Notes
Plan Review Notes For Permit 21101420
Permit Number 21101420
Review Stop B
Sequence Number 1
Notes
Date Text
2021-12-15 10:12:08WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21101420
 ADD: 2400 METROCENTRE BLVD. EAST
 CONT: QUEST CONTRACTING, LLC
 TEL: 561-691-9400
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 14TH/ 2021
 ACTION: DENIED
  
 1) SHEET ALS1.1 & ALS1.2 THE LIFE SAFETY SHEETS:
 1A) ALS1.2. THE CODE INFORMATION PROVIDES THE
 FIRST-FLOOR AREA OF 17,424 SQ. FT. THE QUESTION IS WHAT
 WAS THE 1ST FLOOR SQ. FOOTAGE BEFORE DEMOLITION WHAT IS
 THE SQ. FOOTAGE AFTER THE NEW ADDITION T THE BUILDING?
 107. 2.1.2. ADDITIONAL INFORMATION IS REQUIRED. WILL
 AREA INCREASE FOR FRONTAGE BE REQUIRED?
  
 1B)(1) THE OCCUPANT LOAD FACTOR IS GIVEN BUT THE ACTUAL
 OCCUPANT LOAD PER OCCUPANCY TYPE PER FLOOR IS NOT
 GIVEN. 2020 FBC-BUILDING CODE TABLE 1004.5.
  
 1B)(2) THIS MAY AFFECT THE CORRIDOR WIDTHS FOR
 EDUCATION, TABLE 1020.2 OF THE 2020 FBC-BUILDING.
  
 1C) THE LIFE SAFETY SHEETS DID NOT INDICATE THE AGE OF
 THE CHILDREN WHO WILL BE ATTENDING THIS SCHOOL, THIS
 MAY CREATE ADDITIONAL COMMENTS. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1C) ALS1.1 PLEASE PROVIDE THE COMMON PATH OF TRAVEL
 (DISTANCE AND OCCUPANT LOAD FOR THE BUSINESS AREA) FOR
 THE LARGE CONFERENCE ROOM 135 ONE FOOT OF THE WALL
 LINE. 2020 FBC-B TABLE1006.2.1.
  
 1D) BOTH THE SHEETS ALS1.1 & ALS1.2 SHOW THE STAIRWELL
 #1 / ROOM # 11 PORTIONS OF THE WALLS SHOW A ONE HOUR
 FIRE RATING AND OTHER PARTS OF THE WALLS DO NOT SHOW
 COMPLIANCE WITH 707.3.3 ENCLOSURES FOR INTERIOR EXIT
 STAIRWAYS SHALL COMPLY WITH SECTION 713.4 FIRE
 RESISTANCE RATING.
  
 1E) BOTH THE SHEETS ALS1.1 & ALS1.2 SHOW THE STAIRWELL
 #1 DOORS 011,022, 104, 105,112, 115A, 130, 201 & 205
 ARE ALL LISTED IN THE DOOR SCHEDULE SHEET A6.0 AS
 45-MINUTE DOORS. PLEASE REVIEW TABLE 716.5 AND FIRE
 RATING FOR FIRE DOORS IN INTERIOR EXIT STAIRWAYS, 1
 HOUR.
  
 1F) SHEET ALS1.1 THE 1ST FLOOR DOOR 011 IS LABELED DOOR
 TYPE F PLEASE NOTE THE DOOR VISION PANEL IS LIMITED TO
 100 SQ. INCHES SEE THE 2020 FBC-BUILDING TABLE 716.5
 FOR INTERIOR EXIT STAIRWAYS.
  
 1G) SHEET ALS1.1 THE 1ST FLOOR DOOR 011 ORIGINALLY WAS
 A DOOR WHICH EXITED DIRECTLY TO THE EXTERIOR OF THE
 BUILDING, SEE DEMO PLANS. TH PLANS ARE SILENT AS TO OR
 WHERE A 1-HOUR FIRE RATING IS MAINTAINED TO THE EXIT.
 SHOW COMPLIANCE WITH 10128.1 AND EXCEPTIONS THE
 DISTANCE FROM THE 1-HOUR FIRE RATED DOOR 011 TO THE
 EXIT DOOR 102 IS GREATER THAN 50 FEET.
  
 1H) SHEET ALS1.1 THE 1ST FLOOR. PLEASE PROVIDE A CUT
 SECTION THROUGH THE STAIR # 1 THERE IS A PASSAGE
 BENEATH THE STAIRWAY SHOW THE MINIMUM CEILING HEIGHT
 REQUIREMENTS FOUND IN SECTION 1208.2 OF THE 2020
 FBC-BUILDING CODE.
 1I) SHEET ALS1.1 THE 1ST FLOOR. NOTE #19 INDICATES THE
 FIRE SPRINKLER RISER / STANDPIPE IS LOCATED WITHIN THE
 WALL WITH SMALL DOOR HOW WILL THE FIRE RATING OF 1 HOUR
 BE MAINTAINED. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1J) THE STORAGE ROOM 112 SHOWS ONE-HOUR FIRE RATED
 WALLS BUT DOOR 112 OF THE DOOR SCHEDULE DOES NOT SHOW
 ANY FIRE RATING. PLEASE REVIEW TABLE 716.5 OF THE 2020
 FBC-BUILDING CODE.
  
 1K) THE ELEVATOR EQUIPMENT ROOM140 AND ELECTRICAL ROOM
 106 IT APPEARS IS MISSING A FIRE RATED WALL FOR THE
 ELEVATOR EQUIPMENT ROOM. SEE 2020 FBC-BUILDING 3005.4.
  
 2) SHEET A1.1.5:
 2A) THERE ARE OVER 100 SEATS IN THE DINING ROOM AND THE
 PLANS DO NOT SHOW ACCESSIBLE SEATING. THE LIFE SAFETY
 SHEET DOES NOT SHOW COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY CODE 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 2B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 2C) 902.1. DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORKSTATIONS.
  
 2D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2E) THE KITCHEN ROOM 116 IT APPEARS THERE IS FOOD
 SERVICE LINES. FOOD SERVICE LINES NEED TO SHOW
 COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY CODE
 SECTIONS:
 904.5.1 SELF-SERVING AND DISPENSING DEVICES.
 904.5.2 TRAY SLIDES.
  
 3) SHEET A9.0.1, TYPICAL MOUNTING HEIGHTS- ADULTS
 3A) THE MIRROR IS SHOWN FROM FINISH FLOOR TO THE BOTTOM
 OF THE FRAME 40 INCHES. 603.3 MIRRORS. 2020
 FBC-ACCESSIBILITY CODE. MIRRORS LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 4) SHEETS S1.1.2 & S4.0.1 AND OTHER SHEETS SHOW EITHER
 FIELD WELDING OR BOLTED CONNECTIONS. WELDED OR BOLTED
 CONNECTIONS. THIS BUILDING CONTAINS EITHER BOLTED AND
 OR WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666 OR ACTING CHIEF BUILDING INSPECTOR
 RICHARD BRUNELLE AT 561-805-6670.
  
 5) SUBMITTED PRODUCT APPROVALS FOR ROOF TILE SYSTEMS:
 FL 2533-R26 CERTAINTEED MODIFIED ROOFING SYSTEMS P.
 72OF 75 SUB-SYSTEM R-25 -105MPH VASD
 FL 7473-R9 EAGLE ROOFING PRODUCTS, FLAT ROOF TILE P. 6
 OF 7 6.3.3 ADHESIVE SET.
 ICP ADHESIVE POLYSET AH-160 FL 6332
 FL 6332-R9 ICP ADHESIVE & SEALANTS. P 5 OF 12 TABLE 1
 FIELD TILES IN POLYSET AH-160
 P 6 OF 12 HIP & RIDGE TILE IN POLYSET AH-160 DETAIL 5
 EAST COAST METALS
 FL 9777-R15 OWENS CORNING UNDERLAYMENT 9777.7 PAGE 5 OF
 7 STATES WEATHERLOCK SPECIALTY TILE & METAL (GREEN
 FACER) IS PERMITTED TO BE USED WITH ADHERED CLAY OR
 CONCRETE TILE ROOFING USING DUPONT TILE BOND ROOF TILE
 ADHESIVE.
  
 5A) THE ISSUE WITH THE LISTED ROOFING PRODUCT APPROVAL
 IS WITH FL 9777-R15 OWENS CORNING UNDERLAYMENT 9777.7
 PAGE 5 OF 7 STATES WEATHERLOCK SPECIALTY TILE & METAL
 (GREEN FACER) IS PERMITTED TO BE USED WITH ADHERED CLAY
 OR CONCRETE TILE ROOFING USING DUPONT TILE BOND ROOF
 TILE ADHESIVE. THE ROOFING ADHESIVE DUPONT TILE BOND IS
 NOT THE POLY SET AH-160 LISTED IN THE FL FL 6332-R9 ICP
 ADHESIVE & SEALANTS. P 5 OF 12.
  
 5B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 6) PLEASE SUBMIT THE COMPONENTS AND CLADDING PRODUCT
 APPROVALS. 2020 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (G) PRE-ENGINEERED A/C STANDS
  
 7) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 8A) SHEET S1.1.3 THE ROOF FRAMING PLAN VERSES A2.1.1
 ROOF PLAN. THERE SEEMS TO BE A DISCREPANCY BETWEEN THE
 2 PLANS. SHEET S1.1.3 THE EXISTING ROOF HATCH ON THE
 LOWER ROOF UPPER LEFT-HAND CORNER OF THE PLAN IS TO BE
 REMOVED.
  
 8B) IF THE EXISTING ROOF HATCH ON SHEET S1.1.3 IS TO BE
 REMOVED, THE PLANS ARE SILENT AS HOW ONE IS TO GAIN
 ACCESS TO THIS FLAT ROOF WHERE MECHANICAL EQUIPMENT IS
 TO BE INSTALLED. 2020 FBC-M 306.5 EQUIPMENT AND
 APPLIANCES ON ROOFS OR ELEVATED STRUCTURES.
 WHERE EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE
 LOCATED ON AN ELEVATED STRUCTURE OR THE ROOF OF A
 BUILDING SUCH THAT PERSONNEL WILL HAVE TO CLIMB HIGHER
 THAN 16 FEET ABOVE GRADE TO ACCESS SUCH EQUIPMENT OR
 APPLIANCES, AN INTERIOR OR EXTERIOR MEANS OF ACCESS
 SHALL BE PROVIDED. SUCH ACCESS SHALL NOT REQUIRE
 CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES IN
 HEIGHT OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN
 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT
 SLOPE). SUCH ACCESS SHALL NOT REQUIRE THE USE OF
 PORTABLE LADDERS. WHERE ACCESS INVOLVES CLIMBING OVER
 PARAPET WALLS, THE HEIGHT SHALL BE MEASURED TO THE TOP
 OF THE PARAPET WALL.
  
 8C) IF THE EXISTING ROOF HATCH IS TO BE LEFT IN PLACE
 THE MECHANICAL PLAN M110 HAS RTU 1.3 SITTING PARTIALLY
 ON THE ROOF HATCH.
  
 9) SHEET M110 SHOWS RTU UNITS ON BOTH THE LOWER AND
 UPPER FLAT ROOF DECKS. PLEASE SHOW COMPLIANCE WITH 2020
 FBC-B 1015.7 ROOF ACCESS GUARDS. GUARDS SHALL BE
 PROVIDED WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN
 10 FEET OF A ROOF EDGE OR OPEN SIDE OF A WALKING
 SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN
 30 INCHES ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE
 GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE
 OF A SPHERE 21 INCHES (533 MM) IN DIAMETER.
  
 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT