| Plan Review Notes For Permit 21101412 |
| Permit Number |
21101412 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-12-27 10:51:33 | LIGHT POLES | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE SIGNED AND SEALED LIGHT POLE DETAILS | | | FROM A DESIGN PROFESSIONAL SHOWING THE FOUNDATION AND | | | ATTACHMENTS TO COMPLY WITH THE WIND LOADS - FBC 1609 | | | | | | 2) PLEASE SHOW THE WIND DESIGN DATA USED FOR THE WIND | | | DESIGN PER FBC 1603.1.4 |
|