Plan Review Notes
Plan Review Notes For Permit 21101399
Permit Number 21101399
Review Stop B
Sequence Number 1
Notes
Date Text
2021-11-22 16:46:23BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 21101398
 REVIEWED: NOVEMBER 22, 2021
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2020 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 PLEASE PROVIDE TEST REPORTS TO MEET THE FLOOR TYPE AND
 THICKNESS.
 WHAT IS THE THICHNESS OF FLOOR?
 WHAT IS THE MATERIAL OF FLOOR? CONCRETE?
 REPORTS SHOULD BE FOR PROFLEX SUPER SIM 90
  
 1. [FBC 1207.2]AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH
 OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT
 LESS THAN 45 IF FIELD TESTED, FOR AIR-BORNE NOISE WHEN
 TESTED IN ACCORDANCE WITH ASTM E90.
  
 2. [FBC 1207.3]STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES
 BETWEEN DWELLING UNITS AND SLEEPING UNITS OR BETWEEN A
 DWELLING
 UNIT OR SLEEPING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN
 THE STRUCTURE SHALL HAVE AN IMPACT INSULATION CLASS
 RATING OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 WHEN TESTED
 IN ACCORDANCE WITH ASTM E492.
  
 3. [FBC 603.1]ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 *WE HAVE SOME APPROVED REPORTS AVAILABLE SO PLEASE
 CONTACT ME WITH YOU FLOOR TYPE AND THICKNESS AND I CAN
 SEE IF WE HAVE THE REPORTS ALREADY.
  
 4. PLEASE UPDATE CODE EDITION ON SHEET ID-00 TO FLORIDA
 BUILDING CODE 2020 7TH EDITION
  
 5. THREE OF THE FIVE SHEET SAY PH-1, BUT THE PERMIT
 APPLICATION SAYS PH-3
 IS THIS A COMBINING OF UNITS OR DO THE SHEETS NEED TO
 BE UPDATED?
 COVER, PLAN AND FLOORING PLAN SAY PH1 AND ELEC/PLUMB
 SAY PH3
  
 THERE IS NO DEMO SHEET SO WE DONT SEE EXISTING
 CONDITIONS.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved