2021-11-22 16:49:21BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 21101398
 REVIEWED: NOVEMBER 22, 2021
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2020 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 PLEASE PROVIDE TEST REPORTS TO MEET THE FLOOR TYPE AND
 THICKNESS.
 WHAT IS THE THICHNESS OF FLOOR?
 WHAT IS THE MATERIAL OF FLOOR? CONCRETE?
 REPORTS SHOULD BE FOR PROFLEX SUPER SIM 90
  
 1. [FBC 1207.2]AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH
 OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT
 LESS THAN 45 IF FIELD TESTED, FOR AIR-BORNE NOISE WHEN
 TESTED IN ACCORDANCE WITH ASTM E90.
  
 2. [FBC 1207.3]STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES
 BETWEEN DWELLING UNITS AND SLEEPING UNITS OR BETWEEN A
 DWELLING
 UNIT OR SLEEPING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN
 THE STRUCTURE SHALL HAVE AN IMPACT INSULATION CLASS
 RATING OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 WHEN TESTED
 IN ACCORDANCE WITH ASTM E492.
  
 3. [FBC 603.1]ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 *WE HAVE SOME APPROVED REPORTS AVAILABLE SO PLEASE
 CONTACT ME WITH YOU FLOOR TYPE AND THICKNESS AND I CAN
 SEE IF WE HAVE THE REPORTS ALREADY.
  
 4. WE ONLY HAVE ONE ELECTRICAL SHEET AND ONE PLUMBING
 SHEET IN THE DRAWINGS FOLDER
 PLEASE ADD ANY MISSING SHEETS SUCH AS DEMO AND FLOOR
 PLAN.
 ALSO, NEED MECHANICAL (SEE MECHANICAL COMMENTS)
  
 5. PLEASE UPDATE CODE EDITION ON SHEET ID-00 TO FLORIDA
 BUILDING CODE 2020 7TH EDITION
  