Plan Review Notes
Plan Review Notes For Permit 21101354
Permit Number 21101354
Review Stop B
Sequence Number 1
Notes
Date Text
2021-11-07 08:03:53BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE DESIGN WIND LOAD CALCULATIONS.
 FBC 107.3.5.1.(8) PROVIDE DESIGN LOADS/WIND
 REQUIREMENTS/BUILDING ENVELOPE/STRUCTURAL CALCULATIONS
 PURSUANT TO FBC-CHAPTER 16 OR ASCE 7-16.
 1609.1.1DETERMINATION OF WIND LOADS.
 WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE
 DETERMINED IN ACCORDANCE WITH FBC CHPT. 16 AND/OR
 CHAPTERS 26 TO 30 OF ASCE 7. WIND SHALL BE ASSUMED TO
 COME FROM ANY HORIZONTAL DIRECTION AND WIND PRESSURES
 SHALL BE ASSUMED TO ACT NORMAL TO THE SURFACE
 CONSIDERED.
  
 2. PROVIDE STRUCTURAL CONNECTION DETAIL TO BUILDING.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.