| 2021-12-29 15:01:46 | FAILED |
| | |
| | 1) THE CITYPLACE RETAIL MANAGEMENT APPROVAL STAMP IS |
| | REQUIRED ON THE PLANS. ALTERNATIVELY, YOU MAY PROVIDE A |
| | LETTER FROM CITYPLACE RETAIL MANAGEMENT WHICH APPROVES |
| | THE SPECIFIC PLANS SUBMITTED AS PART OF THE PERMIT. |
| | |
| | 2) PLEASE FULLY DESCRIBE THE PROPOSED USE OF THE SPACE, |
| | INCLUDING WHAT THE "STUDIO" ENTAILS. YOU MUST PROVIDE |
| | THIS INFORMATION SO THAT STAFF CAN VERIFY THAT THE |
| | PROPOSED USE IS PERMITTED AT THIS LOCATION. |
| | |
| | 3) THE ROSEMARY SQUARE DEVELOPMENT REGULATIONS REQUIRE |
| | THAT THE ROSEMARY AVENUE STREET FRONTAGE AT THIS |
| | LOCATION IS REQUIRED TO HAVE A MINIMUM OF 60% |
| | TRANSPARENCY ALONG THE ROSEMARY AVENUE AND THE FERN |
| | STREET FRONTAGES. STAFF REQUIRES CLARIFICATION ON WHAT |
| | IS OCCURRING AT THE STUDIO 1 FRONT WALL WINDOW. |
| | DIFFERING PLANS SHOW A SECOND LAYER OF WINDOWS |
| | INSTALLED WITH THE CROSS SECTION SHOWING AN ACOUSTIC |
| | WALL BETWEEN THE TWO WINDOWS. PLEASE NOTE THAT THE |
| | TRANSPARENCY REQUIREMENTS REQUIRE FULL ABILITY TO SEE |
| | INTO THE STUDIO SPACE FROM THE OUTSIDE OF THE BUILDING. |
| | PROVIDE THE TRANSPARENCY CALCULATIONS. |
| | |
| | 4) THE MECHANICAL FLOOR PLAN SHOWS CU-1A, CONCRETE PAD |
| | AND BOLLARDS ON THE WEST SIDE OF THE BUILDING. WHEN |
| | LOOKING AT GOGGLE STREET VIEW, THESE APPEAR TO BLOCK |
| | THE SIDEWALK AND THE LOADING ZONE. PROVIDED ACCURATE, |
| | DIMENSIONED DRAWINGS SHOWING THE WORK IN THE ALLEY. |
| | PLEASE INCLUDE THE SURVEY THAT THE DRAWINGS ARE BASED |
| | ON WITH THE RESUBMITTAL. NOTE: THE MECHANICAL FLOOR |
| | PLAN AND THE MECHANICAL ISOMETRIC PLAN SEEM TO SHOW THE |
| | CU-1A IN DIFFERENT LOCATIONS RELATIVE TO THE BUILDING |
| | WALL. |
| | |
| | 5) PROVIDE DETAILS OF CU-1A TO INCLUDE HOW IT WILL BE |
| | SCREENED TO ITS FULL HEIGHT. |
| | |