Plan Review Notes
Plan Review Notes For Permit 21101293
Permit Number 21101293
Review Stop P
Sequence Number 1
Notes
Date Text
2021-11-23 17:27:331ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21101293
 11/23/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A200- PROVIDE THE FOLLOWING FBC- ACC
 COMPLIANCE DETAILS:
 A) DETAIL 1- CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER
 CLOSETS- 604.3.
 B) DETAIL 1- CLEAR FLOOR SPACE DIMENSIONS FOR THE
 LAVATORIES- 606.2.
 C) DETAIL 1- TURNING SPACE DIAMETERS- 304.3.
 D) DETAIL 1- CLEAR FLOOR DIMENSIONS FOR SPACE BEYOND
 THE ARC OF THE DOOR- 603.2.3
 E) DETAIL B- HEIGHTS OF THE WATER CLOSET SEATS FROM THE
 FINISHED FLOORS- 604.4.
 F) DETAIL B- HEIGHTS OF THE MIRRORS FROM THE FINISHED
 FLOORS TO THE REFLECTIVE SURFACES- 603.3. THE DETAIL
 DOES NOT SHOW THE MEASUREMENT TO THE REFLECTIVE
 SURFACE.
 G) DETAIL B- REMOVE THE VERTICAL GRAB BARS. THEY ARE
 NOT REQUIRED, AND ALL GRABS ARE TO BE INSTALLED IN A
 HORIZONTAL POSITION- 609.4.
 H) DETAIL B- CENTERLINES OF THE TOILET PAPER DISPENSERS
 MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SECTION
 AND FIGURE 604.7. THE DETAIL DOES NOT SHOW THE
 MEASUREMENT FROM THE FRONT OF THE WATER CLOSET.
 I) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOOR- 606.3.
 J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- 606.2.
  
 2) A-210- PROVIDE THE FOLLOWING FBC- ACC COMPLIANCE
 DETAILS:
 A) CLEAR FLOOR SPACE APPROACH DIAGRAMS AND DIMENSIONS
 AT THE SINK, DISHWASHER, REFRIGERATOR, ICE MAKER, AND
 DISPENSERS SECTIONS 305, 606.2, 804.6.3 & 804.6.6.
 B) REACH RANGES FOR COUNTERTOP DISPENSERS- 308.
 C) OPERABLE PARTS DETAILS FOR APPLIANCES AND
 DISPENSERS- 309.
  
 4) P-000: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES. PLEASE NOTE SERVICE SINKS AND DRINKING
 FOUNTAINS ARE REQUIRED FIXTURES FOR BUSINESS
 OCCUPANCIES.
  
 5) P101: PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1
 WPB.
  
 6) P101: PROVIDE DRAINAGE DISPOSAL FOR THE ICE MAKER-
 SECTION 412 FBC P.
  
 7) P301: THE WATER HEATER DRAIN PAN PIPE SHALL
 TERMINATE OVER A WASTE RECEPTOR, FLOOR DRAIN, OR EXTEND
 TO THE EXTERIOR OF THE BUILDING AND TERMINATE NOT LESS
 THAN 6 INCHES AND NOT MORE THAN 24 INCHES ABOVE THE
 GROUND SURFACE- SECTION 504.7.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  