Plan Review Notes
Plan Review Notes For Permit 21101293
Permit Number 21101293
Review Stop E
Sequence Number 1
Notes
Date Text
2021-12-11 11:51:00ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) GENERATOR, AND LOW VOLTAGE WORK REQUIRE SEPARATE
 PERMITS
  
 2) CONFERENCE ROOMS REQUIRE OUTLET SPACING IN THE FIXED
 WALLS. 210.71.(A)(2)
  
 210.71 MEETING ROOMS
 (A) GENERAL. EACH MEETING ROOM OF NOT MORE THAN 93 M2
 (1000 FT2) IN OTHER THAN DWELLING UNITS SHALL HAVE
 OUTLETS FOR NONLOCKING-TYPE, 125-VOLT, 15- OR 20-AMPERE
 RECEPTACLES. THE OUTLETS SHALL BE INSTALLED IN
 ACCORDANCE WITH 210.71
 (B). WHERE A ROOM OR SPACE IS PROVIDED WITH MOVABLE
 PARTITION(S), EACH ROOM SIZE SHALL BE DETERMINED WITH
 THE PARTITION IN THE POSITION THAT RESULTS IN THE
 SMALLEST SIZE MEETING ROOM. INFORMATIONAL NOTE NO. 1:
 FOR THE PURPOSES OF THIS SECTION, MEETING ROOMS ARE
 TYPICALLY DESIGNED OR INTENDED FOR THE GATHERING OF
 SEATED OCCUPANTS FOR SUCH PURPOSES AS CONFERENCES,
 DELIBERATIONS, OR SIMILAR PURPOSES, WHERE PORTABLE
 ELECTRONIC EQUIPMENT SUCH AS COMPUTERS, PROJECTORS, OR
 SIMILAR EQUIPMENT IS LIKELY TO BE USED. INFORMATIONAL
 NOTE NO. 2: EXAMPLES OF ROOMS THAT ARE NOT MEETING
 ROOMS INCLUDE AUDITORIUMS, SCHOOLROOMS, AND COFFEE
 SHOPS.
 (B) RECEPTACLE OUTLETS REQUIRED. THE TOTAL NUMBER OF
 RECEPTACLE OUTLETS, INCLUDING FLOOR OUTLETS AND
 RECEPTACLE OUTLETS IN FIXED FURNITURE, SHALL NOT BE
 LESS THAN AS DETERMINED IN (1) AND (2). THESE
 RECEPTACLE OUTLETS SHALL BE PERMITTED TO BE LOCATED AS
 DETERMINED BY THE DESIGNER OR BUILDING OWNER.
 (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE
 OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH
 210.52(A)(1) THROUGH (A)(4).
 (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT
 LEAST 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF
 AT LEAST 20 M2 (215 FT2) SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET LOCATED IN THE FLOOR AT A DISTANCE
 NOT LESS THAN 1.8 M (6 FT) FROM ANY FIXED WALL FOR EACH
 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR SPACE.