| 2021-12-11 11:51:00 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2020 7TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| | NFPA 70 2017 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) GENERATOR, AND LOW VOLTAGE WORK REQUIRE SEPARATE |
| | PERMITS |
| | |
| | 2) CONFERENCE ROOMS REQUIRE OUTLET SPACING IN THE FIXED |
| | WALLS. 210.71.(A)(2) |
| | |
| | 210.71 MEETING ROOMS |
| | (A) GENERAL. EACH MEETING ROOM OF NOT MORE THAN 93 M2 |
| | (1000 FT2) IN OTHER THAN DWELLING UNITS SHALL HAVE |
| | OUTLETS FOR NONLOCKING-TYPE, 125-VOLT, 15- OR 20-AMPERE |
| | RECEPTACLES. THE OUTLETS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH 210.71 |
| | (B). WHERE A ROOM OR SPACE IS PROVIDED WITH MOVABLE |
| | PARTITION(S), EACH ROOM SIZE SHALL BE DETERMINED WITH |
| | THE PARTITION IN THE POSITION THAT RESULTS IN THE |
| | SMALLEST SIZE MEETING ROOM. INFORMATIONAL NOTE NO. 1: |
| | FOR THE PURPOSES OF THIS SECTION, MEETING ROOMS ARE |
| | TYPICALLY DESIGNED OR INTENDED FOR THE GATHERING OF |
| | SEATED OCCUPANTS FOR SUCH PURPOSES AS CONFERENCES, |
| | DELIBERATIONS, OR SIMILAR PURPOSES, WHERE PORTABLE |
| | ELECTRONIC EQUIPMENT SUCH AS COMPUTERS, PROJECTORS, OR |
| | SIMILAR EQUIPMENT IS LIKELY TO BE USED. INFORMATIONAL |
| | NOTE NO. 2: EXAMPLES OF ROOMS THAT ARE NOT MEETING |
| | ROOMS INCLUDE AUDITORIUMS, SCHOOLROOMS, AND COFFEE |
| | SHOPS. |
| | (B) RECEPTACLE OUTLETS REQUIRED. THE TOTAL NUMBER OF |
| | RECEPTACLE OUTLETS, INCLUDING FLOOR OUTLETS AND |
| | RECEPTACLE OUTLETS IN FIXED FURNITURE, SHALL NOT BE |
| | LESS THAN AS DETERMINED IN (1) AND (2). THESE |
| | RECEPTACLE OUTLETS SHALL BE PERMITTED TO BE LOCATED AS |
| | DETERMINED BY THE DESIGNER OR BUILDING OWNER. |
| | (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE |
| | OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH |
| | 210.52(A)(1) THROUGH (A)(4). |
| | (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT |
| | LEAST 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF |
| | AT LEAST 20 M2 (215 FT2) SHALL HAVE AT LEAST ONE |
| | RECEPTACLE OUTLET LOCATED IN THE FLOOR AT A DISTANCE |
| | NOT LESS THAN 1.8 M (6 FT) FROM ANY FIXED WALL FOR EACH |
| | 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR SPACE. |