Plan Review Notes
Plan Review Notes For Permit 21101293
Permit Number 21101293
Review Stop B
Sequence Number 1
Notes
Date Text
2021-12-06 09:01:35OFFICE BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE THE EXTERIOR LIGHT GAUGE FRAMING AND
 CLADDING (EFIS) DETAILS TO COMPLY WITH THE WIND LOADS
 FBC 1609
  
 2) PLEASE PROVIDE THE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD
 - FBC WPB 107.3.4
  
 3) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET PAPER
 HOLDER DIMENSION FROM THE FRONT OF THE TOILET PER FBC
 ACCESSIBILITY FBC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 4) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR
 DIMENSION FROM THE FINISHED FLOOR TO THE REFLECTIVE
 SURFACE - FBC ACCESSIBILITY 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 5) ACCESSIBLE RESTROOM - THE VERTICAL GRAB BAR IS NOT A
 REQUIREMENT OF THE FBC ACCESSIBILITY. PLEASE PROVIDE
 THE CLEAR SPACE ABOVE THE GRAB BAR PER FBC
 ACCESSIBILITY 609.3 THE SPACE BETWEEN THE GRAB BAR AND
 PROJECTING OBJECTS ABOVE SHALL BE 12 INCHES (305 MM)
 MINIMUM.