| 2021-12-06 09:01:35 | OFFICE BUILD OUT |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | 1) PLEASE PROVIDE THE EXTERIOR LIGHT GAUGE FRAMING AND |
| | CLADDING (EFIS) DETAILS TO COMPLY WITH THE WIND LOADS |
| | FBC 1609 |
| | |
| | 2) PLEASE PROVIDE THE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS - ALL PRODUCT APPROVALS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD |
| | - FBC WPB 107.3.4 |
| | |
| | 3) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET PAPER |
| | HOLDER DIMENSION FROM THE FRONT OF THE TOILET PER FBC |
| | ACCESSIBILITY FBC 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. |
| | |
| | 4) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR |
| | DIMENSION FROM THE FINISHED FLOOR TO THE REFLECTIVE |
| | SURFACE - FBC ACCESSIBILITY 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 5) ACCESSIBLE RESTROOM - THE VERTICAL GRAB BAR IS NOT A |
| | REQUIREMENT OF THE FBC ACCESSIBILITY. PLEASE PROVIDE |
| | THE CLEAR SPACE ABOVE THE GRAB BAR PER FBC |
| | ACCESSIBILITY 609.3 THE SPACE BETWEEN THE GRAB BAR AND |
| | PROJECTING OBJECTS ABOVE SHALL BE 12 INCHES (305 MM) |
| | MINIMUM. |