| 2022-01-04 11:35:49 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2020 7TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| | NFPA 70 2017 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) NO SMOKE ALARMS SHOWN, SEE FBC RESIDENTIAL CODE |
| | R314, AND 315 |
| | |
| | R314.1 GENERAL. SMOKE ALARMS SHALL COMPLY WITH NFPA 72 |
| | AND SECTION R314. |
| | R315.1 CARBON MONOXIDE PROTECTION. EVERY SEPARATE |
| | BUILDING |
| | OR AN ADDITION TO AN EXISTING BUILDING FOR WHICH A |
| | PERMIT |
| | FOR NEW CONSTRUCTION IS ISSUED AND HAVING A |
| | FOSSIL-FUEL-BURNING |
| | HEATER OR APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, |
| | OR |
| | OTHER FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON |
| | MONOXIDE |
| | AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| | CARBON |
| | MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM |
| | USED |
| | FOR SLEEPING PURPOSES. |
| | |
| | 2) OUTLET REQUIRED AT THE FRONT OF THE HOUSE |
| | 210.52(E)(1) |
| | |
| | 210.52(E)(1) ONE-FAMILY AND TWO-FAMILY DWELLINGS. FOR A |
| | ONE-FAMILY |
| | DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS |
| | AT GRADE |
| | LEVEL, AT LEAST ONE RECEPTACLE OUTLET READILY |
| | ACCESSIBLE FROM |
| | GRADE AND NOT MORE THAN 2.0 M (6 1?2 FT) ABOVE GRADE |
| | LEVEL SHALL |
| | BE INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| | |
| | 3) LIGHT OVER THE TUB SHALL BE INSTALLED PER 410.10(D) |
| | |
| | 410.10(D) BATHTUB AND SHOWER AREAS. NO PARTS OF |
| | CORD-CONNECTED |
| | LUMINAIRES, CHAIN-, CABLE-, OR CORD-SUSPENDED |
| | LUMINAIRES, LIGHTING |
| | TRACK, PENDANTS, OR CEILING-SUSPENDED (PADDLE) FANS |
| | SHALL BE |
| | LOCATED WITHIN A ZONE MEASURED 900 MM (3 FT) |
| | HORIZONTALLY AND |
| | 2.5 M (8 FT) VERTICALLY FROM THE TOP OF THE BATHTUB RIM |
| | OR |
| | SHOWER STALL THRESHOLD. THIS ZONE IS ALL ENCOMPASSING |
| | AND |
| | INCLUDES THE SPACE DIRECTLY OVER THE TUB OR SHOWER |
| | STALL. LUMINAIRES |
| | LOCATED WITHIN THE ACTUAL OUTSIDE DIMENSION OF THE |
| | BATHTUB |
| | OR SHOWER TO A HEIGHT OF 2.5 M (8 FT) VERTICALLY FROM |
| | THE TOP |
| | OF THE BATHTUB RIM OR SHOWER THRESHOLD SHALL BE MARKED |
| | FOR |
| | DAMP LOCATIONS, OR MARKED FOR WET LOCATIONS WHERE |
| | SUBJECT TO |
| | SHOWER SPRAY |