2022-01-04 11:35:49ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO SMOKE ALARMS SHOWN, SEE FBC RESIDENTIAL CODE
 R314, AND 315
  
 R314.1 GENERAL. SMOKE ALARMS SHALL COMPLY WITH NFPA 72
 AND SECTION R314.
 R315.1 CARBON MONOXIDE PROTECTION. EVERY SEPARATE
 BUILDING
 OR AN ADDITION TO AN EXISTING BUILDING FOR WHICH A
 PERMIT
 FOR NEW CONSTRUCTION IS ISSUED AND HAVING A
 FOSSIL-FUEL-BURNING
 HEATER OR APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE,
 OR
 OTHER FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON
 MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED
 FOR SLEEPING PURPOSES.
  
 2) OUTLET REQUIRED AT THE FRONT OF THE HOUSE
 210.52(E)(1)
  
 210.52(E)(1) ONE-FAMILY AND TWO-FAMILY DWELLINGS. FOR A
 ONE-FAMILY
 DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS
 AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET READILY
 ACCESSIBLE FROM
 GRADE AND NOT MORE THAN 2.0 M (6 1?2 FT) ABOVE GRADE
 LEVEL SHALL
 BE INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
  
 3) LIGHT OVER THE TUB SHALL BE INSTALLED PER 410.10(D)
  
 410.10(D) BATHTUB AND SHOWER AREAS. NO PARTS OF
 CORD-CONNECTED
 LUMINAIRES, CHAIN-, CABLE-, OR CORD-SUSPENDED
 LUMINAIRES, LIGHTING
 TRACK, PENDANTS, OR CEILING-SUSPENDED (PADDLE) FANS
 SHALL BE
 LOCATED WITHIN A ZONE MEASURED 900 MM (3 FT)
 HORIZONTALLY AND
 2.5 M (8 FT) VERTICALLY FROM THE TOP OF THE BATHTUB RIM
 OR
 SHOWER STALL THRESHOLD. THIS ZONE IS ALL ENCOMPASSING
 AND
 INCLUDES THE SPACE DIRECTLY OVER THE TUB OR SHOWER
 STALL. LUMINAIRES
 LOCATED WITHIN THE ACTUAL OUTSIDE DIMENSION OF THE
 BATHTUB
 OR SHOWER TO A HEIGHT OF 2.5 M (8 FT) VERTICALLY FROM
 THE TOP
 OF THE BATHTUB RIM OR SHOWER THRESHOLD SHALL BE MARKED
 FOR
 DAMP LOCATIONS, OR MARKED FOR WET LOCATIONS WHERE
 SUBJECT TO
 SHOWER SPRAY