| 2022-02-10 08:36:45 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21101200 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) IN THE SUPPORTING DOCUMENTS FOLDER THERE ARE 2 FILES |
| | NAMED ENERGY CALCULATIONS, ONE IS NAMED ENERGY |
| | CALCULATIONS ? V2 DATED 1/31/2022, THE OTHER IS NAMED |
| | ENERGY CALCLATIONS DATED 10/26/2021. THE FILE DATED |
| | 10/26/2021 IS IN FACT THE ENERGY CALCULATIONS. THE ONE |
| | DATED 1/31/2022 IS LABELED WRONG AS IT IS THE |
| | MECHANICAL EQUIPMENT SIZING CALCULATIONS. PLEASE |
| | CORRECT THIS. |
| | |
| | 2) SHEET M101: THERE IS A NOTE THAT READS FINAL DUCT |
| | ARRANGEMENTS RESERVED PENDING STRUCTURAL COORDINATION. |
| | PLEASE PROVIDE THE FINAL DOCUMENTS AS WE SHOULD BE |
| | REVIEWING THE FINAL CODE COMPLIANT DRAWINGS. IF THESE |
| | ARE THE FINAL DRAWINGS THEN PLEASE REMOVE THE NOTE. FBC |
| | 107.2.1 |
| | |
| | 3) PLEASE MAKE THE RETURN AIR PATH CLEAR IN ALL AREAS. |
| | AHU-1-01 APPEARS TO HAVE THE RETURN TO THE RIGHT SIDE |
| | OF THE CLOSET WITH THE LEFT SIDE OF THE UNIT BEING THE |
| | SUPPLY SIDE. F12 IS LEAVING THE RIGHT SIDE OF THIS UNIT |
| | BUT THE ARROWS INDICTING THE FLOW SHOWS IT IS SUPPLYING |
| | AIR TO THE GUEST SUITE 1. F9 DUCT IS LEAVING FROM THE |
| | LEFT SIDE OF THE UNIT THAT INDICATES A FLOW TO THE |
| | GUEST SUITE 1 BUT THE ARROW AT THE DIFFUSER INDICATES |
| | THE FLOW IS RETURNING BACK TO THE UNIT. FBC 107.2.1 |
| | |
| | 4) PLEASE SHOW THE CONDENSATE DRAIN PIPE SIZES FOR EACH |
| | SECTION OF PIPE. IT APPEARS THAT ALL PIPE SIZES LEAVING |
| | EACH UNIT IS 1 INCH BUT THE ONLY REFERENCE TO THE |
| | DRAINAGE SYSTEM SIZE IS AT THE CONDENSATE GOOSENECK ON |
| | THE EXTERIOR OF THE BUILDING WHICH IS 2 INCH PVC. FBC |
| | RES M1411.3.2 |
| | |
| | 5) PLEASE SHOW THE CALCULATIONS FOR THE CONDENSATE PIPE |
| | SIZING BASED ON FBC M TABLE 307.2.2 |
| | |
| | 6) PLEASE SHOW HOW THIS CONDENSATE DRAINAGE DESIGN WILL |
| | BE CODE COMPLIANT WITH THE DRAIN LINE MAINTENANCE OF |
| | FBC RES M1411.3.3 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |