| Plan Review Notes For Permit 21101194 |
| Permit Number |
21101194 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-08 10:43:22 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 21101194 | | | 11/8/21 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS D101 & A101: REFER TO THE FOLLOWING SECTIONS | | | OF THE FBC EX- (202, 605, 1001.2.1 & 1010.1)- THE PLANS | | | APPEAR TO SHOW A CHANGE IN USE FOR THE BASEMENT LEVEL | | | WHICH MAY RESULT IN AN INCREASED OCCUPANT LOAD AND | | | PLUMBING FIXTURE REQUIREMENTS. PLEASE INDICATE THE | | | PREVIOUS USE AND THE NEW USE, AND PROVIDE PLUMBING | | | FIXTURE CALCULATIONS FOR THE NEW USE IN ACCORDANCE WITH | | | TABLE 403.1 FBC P. PROVIDE A SCHEDULE THAT INDICATES | | | THE REQUIRED AND PROVIDED NUMBER OF FIXTURES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|