| Plan Review Notes For Permit 21101190 |
| Permit Number |
21101190 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-08 12:22:54 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 21101190 | | | 11/8/21 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A301: THE REVISED RESTROOM FLOOR PLANS SHOW | | | THE DOORS SWINGING INTO THE CLEAR FLOOR SPACES FOR THE | | | LAVATORIES WHICH IS NOT ALLOWED PER SECTION 603.2.3 FBC | | | ACC. PLEASE SEE EXCEPTION 2 FOR ADDITIONAL INFORMATION. | | | 2) A701 SANITARY RISER: THE WATER CLOSET AND LAVATORY | | | LOCATIONS IN THE EXECUTIVE RESTROOMS NEED TO BE | | | SWITCHED TO BE CONSISTENT WITH THE CHANGES IN THE FLOOR | | | PLANS- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|