| 2021-12-01 17:54:10 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21101181 |
| | 12/1/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A-110 & A-420: SHOW THE CLEAR FLOOR SPACE |
| | DIAGRAMS AND DIMENSIONS FOR THE 3 NEW SINKS IN THE GAME |
| | ROOM, ARTS/CRAFT ROOM, AND THE 2-COMPARTMENT IN THE |
| | CLOSET- SECTION 606.2 FBC ACC. |
| | |
| | 2) A-420: THE HEIGHT OF THE NEW GAME ROOM SINK FROM THE |
| | FINISHED FLOOR SHALL BE 34 INCHES, NOT 36 INCHES- |
| | SECTION 606.3 FBC ACC. |
| | |
| | 3) A-420: PLEASE PROVIDE ELEVATION HEIGHT DETAILS FOR |
| | THE ARTS/CRAFT AND 2 COMPARTMENT SINKS- SECTION 606.3 |
| | FBC ACC. |
| | |
| | 4) P0.1 & P1.1: SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR THE NEW SINKS AND THE SEDIMENT TRAP- SECTION |
| | 107.2.1 WPB. PLEASE NOTE A COMPLETE REVIEW OF THE |
| | PLUMBING SYSTEMS CANNOT BE COMPLETED WITHOUT THE |
| | SEDIMENT TRAP SPECS. PLEASE INDICATE WHAT TYPE OF |
| | SUBSTANCES WILL BE DRAINED INTO THE TRAP- SECTION |
| | 1003.1 FBC P. |
| | |
| | 5) P1.1: PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 |
| | WPB. |
| | |
| | 6) A1.30: PLEASE PROVIDE CIVIL PLANS SHOWING THE |
| | DISCHARGE LOCATIONS OF THE DOWNSPOUTS TO APPROVED |
| | DRAINAGE LOCATIONS SUCH STORM DRAINS, CATCH BASINS OR |
| | TO GRADED AREAS- SECTION 1101.2 FBC P. |
| | |
| | 7) A5.20: PROVIDE DOWNSPOUT CONNECTION SUPPORT AND |
| | TERMINATION DETAILS. PLEASE NOTE THE SPOUTS SHALL |
| | TERMINATE NOT LESS THAN 1 FT. FROM THE BUILDING- 1101.6 |
| | FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |