2022-01-05 10:07:00RESIDENTIAL (R3) ROOFING REVISION SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 REVISION #21101177
  
 ORIGINAL COMMENT:
 1- FLAT ROOF NOA 20-0131.01 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.2.1 FBC-RESIDENTIAL. NOTE: IF THE SELECTED
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF
 ZONES, THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED. SEE GENERAL LIMITATION #7 ON LAST PAGE OF
 NOA. ASSEMBLIES WITH GENERAL LIMITATION #9 CAN NOT BE
 USED IF THEY DON'T MEET THE DESIGN PRESSURES FOR ALL
 ROOF ZONES.
  
 RESP0NSE:
 PER EMAIL FROM JENNIFER PASCUA LEAD PERMIT COORDINATOR
 - SOUTH CENTRAL AND BUILDPRO, THEY ARE USING THE FIRST
 APPROVED ASSEMBLY ON PAGE 7 OF 18 . THE MAXIMUM DESIGN
 PRESSURES FOR THIS ASSEMBLY IS -52.5PSF. SELECTED
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF
 ZONES. PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS
 FOR NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA.
 NEED THE CALCULATIONS TO MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]