| Plan Review Notes For Permit 21101119 |
| Permit Number |
21101119 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-02 09:28:13 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) PERMIT APPLICATION STATES THIS IS FOR A PANEL | | | CHANGE, THE DRAWINGS SUGGEST MUCH MORE WIRING TO BE | | | DONE | | | 2) VALUATION IS AT $3,800 | | | 3) I ASSUME WHAT IS ON THE DRAWING IS NEW, BUT CAN?T BE | | | SURE | | | 4) I ASSUME POU WATER HEATER IS A TANKLESS STYLE WATER | | | HEATER, IF SO IT IS ONLY LISTED ON THE ATTACHED LOAD | | | CALCULATION AS 4500WATTS. IF THIS THE ONLY WATER HEATER | | | AND IS A TANKLESS IT WOULD BE WAY TOO SMALL | | | 5) NOT ENOUGH DETAIL SHOWING WHAT IS NEW AND WHAT IS | | | EXISTING. IS THERE A NEW A/C, ETC. ? | | | 6) THEY SHOULD SUBMIT A MORE DETAILED DRAWING AND WORK | | | SCOPE THAT CAN BE MORE EASILY UNDERSTOOD | | | | | | |
|